TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
2
North American Emissions Compliance
United States
Canada
Installation
Parts Included
• one TEC3000 Series Thermostat Controller with integral mounting base
• one installation instructions sheet
Location Considerations
Locate the TEC3000 Series Thermostat Controller:
• on a partitioning wall, approximately 5 ft (1.5 m)
above the floor in a location of average
temperature, allowing for vertical air circulation to
the TEC
• away from direct sunlight, radiant heat, outside
walls, outside doors, air discharge grills,
stairwells, and from behind doors
• away from steam or water pipes, warm air stacks,
unconditioned areas (not heated or cooled), or
sources of electrical interference
For integrated passive infrared (PIR) models, be sure
that the thermostat controller is located centrally,
where occupant movement is frequent.
Use insulating foam pads for installations where wiring
passes through the wall to the thermostat.
Note: Allow for sufficient clearance to insert a USB drive into the USB port.
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part
15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in
a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be determined by turning the equipment
off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment
Regulations.
Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur
du Canada.
IMPORTANT: Only connect memory devices to the USB port. Do not use it for charging external devices.
Figure 1: Thermostat Controller
Shown without Occupancy Sensor,
Dimensions, in. (mm)
Display
Security Screw
1-13/32
(36)
4-23/32
(120)
5-5/8
(143)