TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
26
Setting both BIs to the same function is supported for all except Occupancy, Fan Lock, Open Door, and Open
Window. If both BIs are set the same for those four, BI2 is ignored and only BI1 is used.
The Open Door option works in conjunction with a motion sensor, either built into the TEC or connected to another
BI configured for Motion NO/NC mode. When the door is open, motion detected by the sensor is ignored.
Note: Opening the door does not stop an Occupied period started by the motion sensor prior to opening the door.
The polarity of the inputs are provided in Table 9.
Note: Supply Fan Status and Fan Lock are not compatible with each other. The TEC3000 only controls one fan so
it cannot accept feedback from two fan sources. When configuring BI-1 and BI-2, choose either Supply Fan Status
or Fan Lock, but not both.
Aux Control
The TEC has an auxiliary output that can be configured to operate in a few different ways. The Aux Mode supports
seven different options:
Not Used—Output is always off
Occupied NO—Output is normally open, but closes when occupied
Occupied NC—Output is normally closed, but opens when occupied
Occupied Fan NO—Output is normally open, but is closed when occupied with the fan running
Occupied Fan NC—Output is normally closed, but is open when occupied with the fan running
On—Output is turned on (relay closed), used by a BAS to directly control the AUX output
Off—Output is turned off (relay open), used by a BAS to directly control the AUX output
To set the Aux Mode:
1. Press the Menu icon.
2. Press Control Setup.
3. Press General.
4. Press Aux Mode and set accordingly.
5. Press to save and
to return to the previous screen.
Table 9: Input Polarities
BI Configuration Contact Open Contact Closed
Occupancy Unoccupied Occupied
Temp Occ No Trigger Active
Temporary Occupancy Trigger
1
Motion NO No Motion Detected, Standby
Motion Detected, Occupied
1
Motion NC
Motion Detected, Occupied
1
1. Configurations that support both BIs configured for the same feature of the action that occurs when either
of the BIs enter that state.
No Motion Detected, Standby
Dirty Filter Dirty Filter Alarm Inactive
Dirty Filter Alarm
1
Service Service Alarm Inactive
Service Alarm
1
Fan Lock No Airflow Airflow
Open Door Door Open, Unoccupied Door Closed, Occupied
Open Window Window Open, Control Shut Down Window Closed, Control Running
Supply Fan Status Supply Fan Off Supply Fan On