6. RUNNING THE GENERATOR
6.1 Pre-start preparation
Implement pre-start preparations in the following order upon preliminary use.
6.1.1 Fill fuel
Recommended fuel type:
GB/T252-1994 light diesel 0# in summer, -10#, -20#, -30# in winter
● Fill the proper fuel. Improper fuel may lead to risk of fire. Please confirm the type of fuel in
advance.
● Clean any overflowed fuel. Don’t start the engine before cleaning.
● In order to prevent any overflow when machine is running, fill-in amount shall be
approximately 90% of tank volume.
6.1.2 Keynotes fro filling fuel with outside fuel tank
● Ensure tight connection of fuel pipe with the outside fuel tank. Any loose connection may lead
to fuel spill.
● Idle running of fuel feed pump causes damage. Please pay special attention to the fuel level
of outside fuel tank, preventing idle running.
(1) Location of outside fuel tank
Place the outside fuel tank within 5m away from the generator.
In addition, the foundation height for outside fuel tank must be within 0-5m.
Outside fuel tank
Fuel pipe: less than 5m
Generato