EasyManuals Logo
Home>Kohler>Portable Generator>18EFKOZD

Kohler 18EFKOZD User Manual

Kohler 18EFKOZD
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
TP-7044 6/23 39
2.12.2 Communication Setup Submenu
Modbus
®
Communications
The controller communicates using Modbus
®
as a slave connection with the Modbus
®
master initiating the communication. The
controller seeks the system and alternator parameters and diagnostic information then responds back to the Modbus
®
master.
In addition, the controller accepts information to alter controller parameters including generator set starting and stopping. See
Figure 12. Refer to the List of Related Materials for available Modbus
®
literature.
Note:
Only one Modbus
®
master can be connected to the controller. Examples include the remote serial annunciator, monitoring
software, and switchgear applications.
Figure 12 Modbus
®
Connections
A controller can communicate directly to a Modbus
®
master or participate in a network of devices. It can also be used to interface
a local master to a network of devices.
The Modbus
®
master polls slave devices for data. Controller devices are slaves. Examples of master devices are a personal
computer running monitoring software and the remote serial annunciator
SiteTech Group
Parameter
Setting
Modbus
Address
Use a unique network address between 1 and 247 for each unit. Use 1 for a single connection.
Do not use 0 (zero).
Baud rate
9600, 19200, 38400, or 57600.
Must match the master PC and all devices in the system.
Figure 13 Decision-Modbus
®
3500 Communication Parameters
Select the baud rate. Choose the same baud rate for the Modbus
®
master, modems, and connected devices. See Figure 13.
Each generator set controller must have a unique Modbus
®
address and PGEN node number (1-4).
Note:
The PGEN node number is automatically determined. The number of nodes online should match the number of installed
generators.
Note:
The PGEN baud rate should not be adjusted except under direction from a factory service representative. Different baud rates
between controllers on the network will result in a loss of communication on the network.
Modbus
®
is a registered trademark of Schneider Electric.
Generator Set Controller
Modbus
®
Master
RS-232
up to 15 m (50 ft.)
RS-485
up to 1220 m (4000 ft.)

Table of Contents

Other manuals for Kohler 18EFKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 18EFKOZD and is the answer not in the manual?

Kohler 18EFKOZD Specifications

General IconGeneral
BrandKohler
Model18EFKOZD
CategoryPortable Generator
LanguageEnglish

Related product manuals