48 TP-7044 6/23
The engine will run until the coolant temperature is below the Engine Cooled Down parameter setting, or until the Cooldown
Delay has expired.
The cooldown cycle lasts for some predetermined amount of time. The cooldown delay is an adjustable parameter. The Engine
Cooled Down temperature is not adjustable.
Note:
No engine cooldown cycle occurs if the OFF button is pressed or if a fault occurs. The shutdown is immediate. If possible, run
the generator set without load for 5 minutes to ensure adequate engine cooldown.
Button Mode
Generator Set Status
Fault
Lamp
Alarm
Horn
Alarm Silence
Button
Alarm Horn
Lamp
Controller Display
AUTO
Off
Off
Scrolling Overview Menu
Only
On (or Cranking)
Off
Running and then Off
Red
On
Shutdown Message
Off
Pressed
Yellow
OFF/RESET
Off
Yellow
On
Not In Auto Warning
Off
Pressed
Yellow
RUN
(unit fails to start)
Off (or Cranking)
Yellow
On
Not in Auto Warning
Off
Pressed
Yellow
Off
Red
On
Locked Rotor Shutdown
(or other shutdown
message)
Off
Pressed
Yellow
RUN
(unit starts)
Off (or Cranking)
Yellow
On
Not in Auto Warming
On
Off
Pressed
Yellow
Running and then Off
Red
On
Shutdown Message
Off
Pressed
Yellow
Figure 16 Button Function Summary
2.14.1 Emergency Stop
Use the controller emergency stop switch for immediate emergency shutdown.
The emergency stop switch bypasses the time delay engine cooldown and immediately shuts down the generator set.
Note:
Use the emergency stop switch(es) for emergency shutdowns only. Use the generator set OFF/RESET button for normal
shutdowns.
The controller fault lamp lights and the unit shuts down when the local emergency stop switch activates.
Use the following procedure to reset the generator set after shutdown by a local or remote emergency stop switch. Refer to the
Controller Resetting (Following System Shutdown or Warning) section, Controller Resetting procedure, to restart the generator
set following a fault shutdown.
1. Investigate and correct the cause of the emergency stop.
2. Reset the controller emergency stop switch by pulling the switch dial outward.
3. Press the generator set OFF/RESET button.
4. After resetting all faults using the controller reset procedure in the Controller Resetting (Following System Shutdown or
Warning) section, press the generator set RUN and/or AUTO button to restart the generator set. The generator set will
not crank until the reset procedure completes.

Table of Contents

Other manuals for Kohler 18EFKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 18EFKOZD and is the answer not in the manual?

Kohler 18EFKOZD Specifications

General IconGeneral
BrandKohler
Model18EFKOZD
CategoryPortable Generator
LanguageEnglish

Related product manuals