TP-6772 2/14b 23Section 2 Operation
Event Log Menu
This menu allows the user to review up to 1000 entries of
system events including shutdown faults, warning
faults, and status events. See 2.6.6 Controller Fault
Diagnostics for a list of the items that appear on the
Event Log.
Prime Menu
This menu, if confirmed, allows the user to initiate the
electric fuel pump to prime the fuel system.
Volt Select Menu
Note: The generator set must be stopped before
changing the voltage selection.
This menu allows the user to readily change controller
voltage settings.
Note: The generator set output leads require voltage
reconnection. See the installation manual for
voltage reconnection information.
With the generator set stopped, go to the Volt Select
menu. Then push and hold the pushbutton/rotary
selector dial until the voltage selection starts to flash.
Volt selection is now available. Scroll to the desired
voltage and momentarily press the pushbutton/rotary
selector dial to confirm the voltage selection.
The displays for Volt Select appear as shown in the
following list.
D 120/240 V 1 Ph (3 wire)
D 120/208 V 3 Ph (4 wire Wye)
D 139/240 V 3 Ph (Wye)
D 277/480 V 3 Ph (Wye)
D 120/240 V 3 Ph (Delta)
D 115/230 V 1 Ph (3 wire)
D 120 V 1 Ph (2 wire)
D 230 V 1 Ph (2 wire)
D 240 V 1 Ph (2 wire)
D 110/190 V 3 Ph (Wye)
D 127/220 V 3 Ph (Wye)
D 115/230 V 3 Ph (Delta)
D 230/400 V 3 Ph (Wye)
D 240/416 V 3 Ph (Wye)
2.6.6 Controller Fault Diagnostics
This table provides descriptions of the system events
and their types—warning, shutdown, status, and notice.
Warnings show green/red fault lamp and signal an
impending problem. Shutdowns show red fault lamp
and stop the generator set. Status is an event that is not
an alert but is part of the event history. Notice is an alert
that is NOT part of the event history. System events are
available as a Relay Output as shown.
Throughout this manual there are examples of the
display text. In some cases, the message words and
phrases are abbreviated or shortened to accommodate
the number of characters in the 1 2 x 2 digital display.
See the following table for a full description of the system
event display messages.

Table of Contents

Other manuals for Kohler 7-9EFKOZD

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 7-9EFKOZD and is the answer not in the manual?

Kohler 7-9EFKOZD Specifications

General IconGeneral
BrandKohler
Model7-9EFKOZD
CategoryMarine Equipment
LanguageEnglish

Related product manuals