Section 6 Decision-Makerr 3000 ControllerTP-6356 4/12
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
General Functions
Alarm silence, 0--Auto only
(NFPA 110), 1--Always
AlarmSilenceMode S A 0--1 1
Aux. inputs 0--5 VDC, 1 analog Aux Input Warning 0--100% 100% 0--10 0
Aux. inputs 0--5 VDC, 1 analog Aux Input Shutdwn 0--100% 100% 0--10 0
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Warning
0--10
(0--30
inhibit)
0(0
inhibit)
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Shutdwn
0--10
(0--30
inhibit)
0(0
inhibit)
Backup parameters loaded Backup Pars Status Not adjustable
Battery charger fault * Batt Chg Flt Warning Not adjustable
Chicago code active * Auto Locked Notice
Common fault Common Fault
Shutdwn
Not adjustable
Common warning Common Warng Not adjustable
Default parameters loaded Default Pars Warning Not adjustable
Emergency stop Emerg Stop Shutdwn Not adjustable
Engine cooldown (delay)
active
Eng Cooldown Notice
Engine start delay active Start Delay Notice
Engine started Engine Start Status Not adjustable
Engine stopped Engine Stop Status Not adjustable
EPS supplying load Emerg Pwr On Notice Not adjustable
File system error (controller
fault)
File Error Shutdwn Not adjustable
Generator running Gen Running Notice Not adjustable
Input/output (optional module
board) communication loss
OB1 Com Loss Not adjustable
Internal failure Intern Error Shutdwn Not adjustable
Measurement Units,
0--English, 1--Metric
Measurement Display DS A 0--1 1
Metering communication loss MeterCommLos
Shutdwn
Not adjustable
NFPA 110 alarm active NFPA Alarm Notice
Not in auto (master control
buttons)
Not In Auto Warning Not adjustable
Prime power application,
0--Standby, 1--Prime
Power Type DS A 0--1 0
Remote start Remote Start Status Not adjustable
System ready System Ready Status Not adjustable
System timer failed TimerErrorNotice Not adjustable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 3+ and is the answer not in the manual?

Kohler Decision-Maker 3+ Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 3+
CategoryPortable Generator
LanguageEnglish

Related product manuals