Section 6 Decision-Makerr 3000 Controller TP-6356 4/12
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
Generator Functions
AC sensing loss AC Sens Loss
Warning
Not adjustable
AC sensing loss AC Sens Loss
Shutdwn
Fixed 3 Not adjustable
Alternator protection Alt Protect Shutdwn Not adjustable
Ground fault input * Ground Fault Warning Not adjustable
kW overload
Total Power High
Shutdwn
Fixed
102%
standby,
112%
prime
Fixed 60 Not adjustable
Locked rotor (failed to crank) Locked Rotor Shutdwn S A 1--5 5
Overfrequency Freq High Shutdwn 102--140% 110% Fixed 10 Not adjustable
Overvoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) High
Shutdwn
S A 105--135% 120% 2--10 2
Power rating Pwr Rating DS S 10--5000 275
System frequency System Freq DS S 50--60 60
System voltage System Volt DS S 110--600 208
Underfrequency Frequency Low
Shutdwn
80--95% 90% Fixed
10 ST
60 LT
Not adjustable
Undervoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) Low
Shutdwn
S A 70--95% 80% 5--30 10
Voltage/phase configuration,
0--Single phase, 1--Single
phase dogleg, 2--three phase
wye, 3--three phase delta
SystemPhase DS S 0--3 2
Voltage regulator average
voltage adjustment
VR Volt Adj DS R 108--600 208
(Voltage) regulator
communication loss
RegCommLoss
Shutdwn
Not adjustable
SiteTech Read/Write Display Only
Current transformer ratio ]
S S 1-- 1200
ECM power S S 0--1 0
Engine cooldown delay S A 0--600 300
Engine (cyclic) crank on S A 10--30 15
Engine (cyclic) crank pause S A 1--60 15
Engine ECM start delay S A 0--300 0
Engine idle duration S A 0--60 60
Engine no. of (cyclic) crank
cycles
S S 1--6 3
Engine restart delay S A 1--10 10
Engine start aid delay S A 0--10 0
Engine start delay S A 0--300 0
System battery voltage ]
S S 12--24 12
Voltage regulator gain S R 1--255 128
Voltage regulator stability
adjust
S R 1--255 128
Voltage regulator, volts per
Hertz slope
S R 1--10 5
Voltage regulator, volts per
Hertz cutin frequency
S R 42--62 57.5
* Some functions require optional input sensors or are engine ECM dependent on some generator set models.
[ ECM inputs are engine manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
ST--Short Term, LT--Long Term