EasyManuals Logo
Home>Lamtec>Transmitter>LT3-F

Lamtec LT3-F User Manual

Lamtec LT3-F
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
79
10 Options
10.4 LSB Module for Calculating Combustion Efficiency
10.4.1 Functional Description
Properties:
Two Pt100 temperature inputs to record the flue gas temperature and inlet temperature
Two analogue outputs 0/4 ... 20 mA to emit the flue gas temperature and its efficiency
Power supply 24 VDC / 50 mA (PELV)
NOTICE
All outgoing lines from the LSB module must be screened. The screens must be applied to the
PE rail as short as possible.
Description of function
The calculation takes place according to the following formula:
n
F
= 100 (q
Af
+ q
Ag
) %
q
Af
= flue gas loss due to free heat
q
Ag
= flue gas loss due to bound heat
q
Af
= ( t
A
- t
L
) * [A
2
/ 21 – O
2
+ B]
The calculation of the flue gas losses is based on the following mean fuel values:
Oil A
2
= 0.68; B = 0.007
Gas A
2
= 0.66; B = 0.009
It is assumed that the combustion takes place free of CO and soot. The flue gas losses due
to bound heat q
Ag
are not taken into consideration.
Function not effective until < 14.9 vol. % O
2
.
Display:
NOTICE
The termination resistor (120 ) must be installed and activated on the first and the last BUS
device.
Avoid transmission line!
The terminal resistance can be set via DIP switch 1.
ETA efficiency 0 ... 100%
T-ex flue gas temperature 0 ... 400 °C
T air inlet air temperature 0 ... 400 °C

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lamtec LT3-F and is the answer not in the manual?

Lamtec LT3-F Specifications

General IconGeneral
BrandLamtec
ModelLT3-F
CategoryTransmitter
LanguageEnglish

Related product manuals