EasyManuals Logo
Home>LEGRAND>UPS>Keor MOD Series

LEGRAND Keor MOD Series User Manual

LEGRAND Keor MOD Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
28
7. Warehousing
DANGER
All storage operations must be carried out only by a SKILLED TECHNICIAN (paragraph 2.2.1)
DANGER
A SKILLED TECHNICIAN must check that there is no voltage present before disconnecting the cables. All the
battery isolator switches on the UPS and on the EBC must be open.
All the battery isolator switches on the UPS and on the external battery cabinets must be open. The battery
drawers of the UPS and of the external battery cabinet (if present) must be removed.
7.1 UPS
The UPS must be stored in an environment with a room temperature between -20°C (-4°F) and +50°C (+122°F) and
humidity less than 90% (not condensing).
7.2 Batteries
It is possible to store batteries without recharging them in the following conditions:
- up to 6 months at +20°C (+68°F);
- up to 3 months at +30°C (+86°F);
- up to 2 months at +35°C (+95°F).
CAUTION
Batteries must never be stored if partially or totally discharged.
LEGRAND is not liable for any damage or bad functioning caused to the UPS by wrong warehousing of the batteries.

Other manuals for LEGRAND Keor MOD Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LEGRAND Keor MOD Series and is the answer not in the manual?

LEGRAND Keor MOD Series Specifications

General IconGeneral
BrandLEGRAND
ModelKeor MOD Series
CategoryUPS
LanguageEnglish

Related product manuals