• 10 •
l/h kPa kW kW kW
10 °C
345 12 --- --- --- 1,90 3,39
495 20 --- --- --- 1,90 3,40
700 39 --- --- --- 1,91 3,42
15 °C
345 12 2,05 6,06 0,70 2,20 3,76
495 20 2,09 6,90 0,70 2,19 3,75
700 39 2,12 7,58 0,69 2,18 3,75
20 °C
345 12 1,97 4,93 0,71 2,49 4,09
495 20 2,01 5,44 0,71 2,50 4,10
700 39 2,04 5,83 0,70 2,51 4,11
25 °C
345 12 1,93 4,52 0,72 2,82 4,43
495 20 1,89 4,16 0,72 2,83 4,44
700 39 1,96 4,78 0,71 2,84 4,45
30 °C
345 12 1,81 3,58 0,74 --- ---
495 20 1,85 3,85 0,73 --- ---
700 39 1,88 4,04 0,73 --- ---
35 °C
345 12 1,71 3,08 0,76 --- ---
495 20 1,76 3,32 0,75 --- ---
700 39 1,79 3,47 0,74 --- ---
40 °C
345 12 1,61 2,65 0,78 --- ---
495 20 1,66 2,85 0,76 --- ---
700 39 1,69 2,98 0,76 --- ---
l/h kPa kW kW kW
10 °C
390 16 --- --- --- 2,88 3,93
560 24 --- --- --- 2,89 3,93
800 41 --- --- --- 2,90 3,94
15 °C
390 16 3,15 7,24 0,69 3,26 4,30
560 24 3,10 6,77 0,70 3,25 4,29
800 41 3,02 6,14 0,70 3,24 4,29
20 °C
390 16 3,02 6,18 0,70 3,69 4,70
560 24 2,97 5,83 0,71 3,70 4,70
800 41 2,89 5,33 0,72 3,71 4,71
25 °C
390 16 2,89 5,34 0,72 4,28 4,94
560 24 2,84 5,06 0,72 4,29 4,93
800 41 2,75 4,64 0,73 4,30 4,94
30 °C
390 16 2,75 4,64 0,73 --- ---
560 24 2,70 4,40 0,74 --- ---
800 41 2,62 4,05 0,75 --- ---
35 °C
390 16 2,61 4,04 0,75 --- ---
560 24 2,56 3,84 0,75 --- ---
800 41 2,48 3,54 0,76 --- ---
40 °C
390 16 2,47 3,50 0,77 --- ---
560 24 2,41 3,33 0,77 --- ---
800 41 2,33 3,06 0,79 --- ---
AWH 002
485 m
3
/h
AWH 003
550 m
3
/h
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
1.8.- CAPACITY TABLES
Water fl ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Water fl ow
Water
pressure drop
AWC/AWH
COOLING CAPACITY
AWH
HEATING CAPACITY
Total capacity EER Sensible/Total Total capacity
Total absorbed
power
Water inlet temperature
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Minimum
Nominal
Maximum
Nominal operating conditions:
Exchanger air inlet temperature: 27ºC DB/19ºC WB in cooling mode and 20ºC WB
in heating mode.
(DW:dry bulb / WB:wet bulb)
For another working conditions use correction factor tables.
GENERAL CHARACTERISTICS
Nominal airfl ow rate
Nominal airfl ow rate