3
1
2
12 3
AWH 002 / AWH 003 230V / 1Ph 3 x 1,5 mm² -
AWC/H 007 - AWC/H 008 230V / 1Ph 3 x 2,5 mm² 3 x 10 mm²
AWC/H 010 230V / 1Ph 3 x 6 mm² 3 x 16 mm²
AWC/H 012
230V / 1Ph 3 x 6 mm² 3 x 16 mm²
400V / 3Ph+N 5 x 2,5 mm² 5 x 6 mm²
AWC/H 015 400V / 3Ph+N 5 x 2,5 mm² 5 x 6 mm²
AWC/H 018 - AWC/H 020 400V / 3Ph+N 5 x 4 mm² 5 x 10 mm²
AQUALEAN - AWC/AWH - MIL118E-1407 / 10-2013
GENERAL CHARACTERISTICS
1.5.- ELECTRICAL CONNECTIONS.
1 - Power supply
2 - Power supply with electrical heater (units 007 to 020).
3 - Connection control.
F
O
R ELE
C
TRI
C
AL
CO
NNE
C
TI
O
N REFER T
O
WIRIN
G
DIA
G
RAM IN THE
U
NIT.
INSTALLATION GUIDE FOR CONTROL CABLE
(
TO AVOID INTERFERENCES
):
Use the screened 15 m cable supplied with terminal (3 wires + screen).
sc
Wire the cable separated
f
rom electrical power wirin
g
b
y
a ph
y
sical distance o
f
500 mm.
Wire the cable separated
f
rom halo
g
en lamps
/
uorescent tube li
g
htin
g
... b
y
a ph
y
isical distance o
f
500 mm.
Wire the cable separated
f
rom radio
f
requenc
y
sources such as radio transmitter... at least 500 mm.
NEVER WIND THE REMAININ
G
C
ABLE AR
O
UND,
C
UT THE
C
ABLE BY THE TERMINAL END.
Local and national le
islation has to be taken into account when the unit will be installed.
E.Box
EH
MODEL
VOLTAGE
50Hz
WIRE NUMBER AND SECTION
5 X 1 mm² shielded