• 24 •
TRMO
ABA054 ARA073 ARA081
TGEL10-6.5 TGEL10-9 TGEL10-9
2.5 kg 3.5 kg 4.5 kg
BALTIC-IOM-0412-E / Installation manual
THERMODYNAMIC HEAT RECOVERY - SERVICE MANUAL
1. REFRIGERATION CIRCUIT
Frigori c components access:
Compressor is located in the x condenser part. Its access for electrical checking and
pressure taps (HP and LP) is made through the screwed access door behind the hinged
coil.
4-way valve, thermostatic expansion valve, dryer, and sensors are located on the
e-Drive™ supply compartment.
C-box D-box E-box
Compressors
Thermostatic expansion valves
Refrigerant load
WARNING! During the settings, wait until the economizer is fully closed or opened, since it takes 1-2 minutes
to switch.
Electrical components:
For D and E-box, speci c TRMO components are located in the electrical box.
For C-box, speci c TRMO components are located on the back of the electrical box, and can be accessible from the supply e-Drive™
compartment.
Circuit speci cations:
2. COMMISSIONING
Electrical connections:
All wire connections are factory made.
Starting up:
• CLIMATIC™ con guration:
- Power the unit
- Check the con guration of the CLIMATIC™ 60 with the DS60 in expert mode. See § Control Manual / Con guration
Flow rate settings:
Make sure that both supply and exhaust air ow are balanced. See section EBHO or ERVF. Balancing is correctly set if:
- with Test = 'B.Nom 100%': at 100% fresh air, set the exhaust Flow 3864 = supply ow 3333;
- then switch Test = 'B.Nom 0%':
1. reduce coef cient 3866 until the louvers are closed;
2. then if the ow (supply and exhaust) is far from the previous ow settings, set coef cient 3335;
3. nally, repeat step 1 and 2 to obtain a constant ow whatever the fresh air mode.
- same settings have to be realized for reduced ow - 3334 and 3865.
Start the TRMO circuit (circuit 3): switch Test='C3--Cool'
- check the sense of rotation of the circuit 3 compressor;
- check frigori c values (HP, LP, overheating and subcooling).
Repeat the last operations with Test='C3--Heat'

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BAC 045 DNM 3M and is the answer not in the manual?

Lennox BAC 045 DNM 3M Specifications

General IconGeneral
BrandLennox
ModelBAC 045 DNM 3M
CategoryAir Conditioner
LanguageEnglish

Related product manuals