BALTIC-IOM-0412-E / Service manual
GAS BURNERS
Standard start-up chronology
Time in seconds
Operations
Control operation sequence
Extraction fan
Smoke extraction fan "ON"
30 to 45 seconds pre-ventilation
Fire-up spark electrode 4s
Opening of the gas valve
"high heat"
Flame propagation towards the
ionisation probe
If ionisation within 5sec:normal
running
Otherwise fault on gas ignition
control block
After 5 minutes, fault reported on
the CLIMATIC™ controller
If incorrect sequence, refer to the fault analysis table to identify the problem.