• 45 •
12 16,3 10,8 17,0 11,8 17,8 12,8
24 32,6 21,5 34,0 23,5 35,6 25,6
27 36.7 24.3 38.3 26.6 40.1 28.8
36 48,9 32,3 51,1 35,3 53,3 38,4
45 61.1 40.5 63.8 44.3 66.8 48.0
48 65,2 43,0 68,1 47,0 71,1 51,3
54 73,4 48,4 76,6 52,9 80,0 57,7
BALTIC-IOM-0412-E / Service manual
HEATING OPTIONS
Electric heater
The BALTIC™ electric heaters are stand alone options which are tted in the heating section of the unit. As for the hot water coil or
the gas burner this option slides into the heating compartment located under the supply fan.
In order to reduce the pressure drops the air ow is ducted around the shielded resistances. The resistances are made smooth stainless
steel tubes with a capacity of 6W/cm
2
.
It is protected as standard, against overheat via a high temperature overload protection set at 98°C and located less than 150mm
after the heater itself.
There are three sizes available for each size of unit:
S: Standard heat
H: High heat
The standard heat electric heaters are staged control with 50% or 100%. The high heat version is controlled through a fully modulating
triac.
380V 400V 415V
Module size
(kW)
Current (A) Cap (kW) Current (A) Cap (kW) Current (A) Cap (kW)
WARNING: electric heater is connected heater to mains power – risk of electrical shock – switch off the unit
prior to open this section

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox BAC 045 DNM 3M and is the answer not in the manual?

Lennox BAC 045 DNM 3M Specifications

General IconGeneral
BrandLennox
ModelBAC 045 DNM 3M
CategoryAir Conditioner
LanguageEnglish

Related product manuals