EasyManuals Logo
Home>Lennox>Air Conditioner>BAG065DHM

Lennox BAG065DHM User Manual

Lennox BAG065DHM
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #100 background imageLoading...
Page #100 background image
CLIMATIC 50 ROOFTOP VERSION 23
BALTIC R410A-IOM-0708-E Page 99
Analog Inputs
The following items can be used for each input:
[Not Used]..........................Not used
[S.P Offset]......................... Room temperature set point offset 4-20mA signal.
[F.A Offset].........................Minimum fresh air set point 4-20mA signal.
[Weather T.] ....................... Entry for a Meteorological temperature sensor
[Weather H.].......................Entry for a Meteorological humidity sensor
[Free NTC] ......................... Free temperature probe connection
[Free Hr.]............................ Free relative humidity sensor connection
Ambient Temperature Set Point Offset 4-20mA Signal:
The 4-20mA signal sent to the unit is linearly converted using a -5K to +5K range of temperature set point.
For example: for a unit set point of 20°C
A 4mA signal will give a 15°C unit temperature set point
A 12mA signal will give a 20°C unit temperature set point
A 20mA signal will give a 25°C unit temperature set point
Minimum Fresh Air Set Point 4-20mA Signal:
The 4-20mA signal sent to the unit is linearly converted to a 0% - 100% fresh air damper opening request.
Entry for a Meteorological Temperature Sensor:
The 4-20mA signal sent to the unit is linearly converted using a -40°C to +80°C range, this measure will replace the one
given by the unit sensor.
Input for a Meteorological Sensor for Relative Humidity:
The 4-20mA signal sent to the unit is linearly converted using a 0% to 100% range, this measure will replace the one given
by the unit sensor.
Free Temperature Probe Connection:
Lennox NTC sensor.
Free Relative Humidity Sensor Connection:
The 4-20mA signal sent to the unit is linearly converted using a 0% to 100% range.
Example BE50-
J9.B1,
BE50-J9.B2
4/20mA Signal
- +
NTC
Probe