CLIMATIC 50 ROOFTOP VERSION 23
BALTIC R410A-IOM-0708-E Page 110
@ (hexa)
@ (deci)
DS50
3FH 63 R bit
[Alarm]
bit.0 = Probes & Sensors
bit.1 = Fan, Blower
bit.2 = Low Temperature, Condenser Water
bit.3 = High Temperature, Condenser Water
bit.4 = Flow Switch, Condenser Water
bit.5 = Smoke Detector
bit.6 = Fans, Condenser
bit.7 = Compressor 1, H.P. & I.P.
bit.8 = Compressor 1, L.P.
bit.9 = Compressor 2, H.P. & I.P.
bit.10 = Compressor 2, L.P.
bit.11 = Compressor 3, H.P. & I.P.
bit.12 = Compressor 3, L.P.
bit.13 = Compressor 4, H.P. & I.P.
bit.14 = Compressor 4, L.P.
bit.15 =
40H 64 R not used