CLIMATIC 50 ROOFTOP VERSION 23
BALTIC R410A-IOM-0708-E Page 111
LonWorks
Type
In
de
x
pC
O
Name NV Type NV Direction
Index
pCO
DS50
ANL 1
I_Sp_T_Cool_BMS 105
input 1
ANL 1
O_Sp_T_Cool_BMS 105
output 1
[Occupation][Room SP] Required maximum
room temperature in °C. Cooling set point
3322
(BMS)
ANL 2
I_Sp_T_Heat_BMS 105
input 2
ANL 2
O_Sp_T_Heat_BMS 105
output 2
[Occupation][Room SP] Required minimum
room temperature in °C. Heating set point
3323
(BMS)
ANL 3
I_Sp_T_Cool_Uno 105
input 3
ANL 3
O_Sp_T_Cool_Uno 105
output 3
[Unoccupied][Room SP] Required maximum
room temperature in °C. Cooling set point
3322
(Uno)
ANL 4
I_Sp_T_Heat_Uno 105
input 4
ANL 4
O_Sp_T_Heat_Uno 105
output 4
[Unoccupied][Room SP] Required minimum
room temperature in °C. Heating set point
3323
(Uno)
ANL 5
I_Sp_Hr_Dehu_BMS 81
input 5
ANL 5
O_Sp_Hr_Dehu_BMS 81
output 5
[Humidity] Desired Maximum relative humidity
in Room (in %). Dehumidification set point.
3341
(BMS)
ANL 6
I_Sp_Hr_Humi_BMS 81
input 6
ANL 6
O_Sp_Hr_Humi_BMS 81
output 6
[Humidity] Desired Minimum relative humidity
in Room (in %). Humidification set point.
3342
(BMS)
ANL 17
O_T_Room 105
output 17
[Temperature] Room 2112
ANL 18
O_T_Outside 105
output 18
[Temperature] Outdoor 2111
ANL 19
O_Ia_T_Supply 105
output 19
[Temperature] Supply 2113
ANL 20
O_Hr_Room 81
output 20
[Relative Humidity] Room 2122
ANL 21
O_Ha_Room 23
output 21
[Absolute Humidity] Room 2124
ANL 22
O_Hr_Outside 81
output 22
[Relative Humidity] Outdoor 2121
ANL 23
O_Ha_Outside 23
output 23
[Absolute Humidity] Outdoor 2123
INT 1
I_Sp_BMS_Dog 8
input 208
INT 1
O_Sp_BMS_Dog 8
output 208
[ BMS ] Activation of the control by a computer
or an automat - mode BMS is activated if this
value is different from zero, This value is
decreased every second
3932
INT 2
I_Sp_EcoMini_BMS 8
input 209
INT 2
O_Sp_EcoMini_BMS 8
output 209
[Room SP] Required room minimum fresh air
rate in % Middle of the dead zone.
3312
(BMS)
INT 3
I_Hour 8
input 210
INT 3
O_Hour 8
output 210
[Clock] Hour 3121
INT 4
I_Minute 8
input 211
INT 4
O_Minute 8
output 211
[Clock] Minute 3122
INT 5
I_Day 8
input 212
INT 5
O_Day 8
output 212
[Clock] Day of the month 3123
INT 6
I_Month 8
input 213
INT 6
O_Month 8
output 213
[Clock] Month 3124
INT 17
O_Error_Codes 8
output 224
[Alarm] Code Error 1000
INT 18
O_Oa_Eco 81
output 225
[% of opening] Damper of fresh air 2413
INT 19
O_Oa_GasHeat 81
output 226
[% of opening] Valve gas 2618
INT 20
O_Oa_TriacHeat 81
output 227
[% of opening] Electrical heaters (Triac) 2627
INT 21
O_Oa_HotWater 81
output 228
[% of opening] Hot water coil 2633
DGT 1
I_Sp_On_Unit 95
input 415
DGT 1
O_Sp_On_Unit 95
output 415
[On / Off] Unit 3111
DGT 2
I_Sp_Reset 95
input 416
DGT 2
O_Sp_Reset 95
output 416
[Reset] Discharges the safety measures of the
unit
3112
DGT 3
I_Sp_Unoc 95
input 417
DGT 3
O_Sp_Unoc 95
output 417
[BMS] Activation of the Unoccupied mode [Off]
Occupied mode - [On] Unoccupied mode
3933
DGT 4
I_Clock 95
input 418
[Clock] [OFF] read hour & minute [ON] write
hour & minute
DGT 17
O_Od_Alarm 95
output 431
[Alarm] General 1000