CLIMATIC 50 – ROOFTOP – VERSION 23
BALTIC R410A-IOM-0708-E Page 111
LonWorks
Type
In
de
x
pC
O
Name NV Type NV Direction
Index
pCO
DS50
ANL 1
[Occupation][Room SP] Required maximum
room temperature in °C. Cooling set point
3322
(BMS)
[Occupation][Room SP] Required minimum
room temperature in °C. Heating set point
3323
(BMS)
[Unoccupied][Room SP] Required maximum
room temperature in °C. Cooling set point
3322
(Uno)
ANL 4
[Unoccupied][Room SP] Required minimum
room temperature in °C. Heating set point
3323
(Uno)
ANL 5
[Humidity] Desired Maximum relative humidity
in Room (in %). – Dehumidification set point.
3341
(BMS)
[Humidity] Desired Minimum relative humidity
in Room (in %). – Humidification set point.
3342
(BMS)
[Temperature] Room 2112
ANL 18
[Temperature] Outdoor 2111
ANL 19
[Temperature] Supply 2113
ANL 20
[Relative Humidity] Room 2122
ANL 21
[Absolute Humidity] Room 2124
ANL 22
[Relative Humidity] Outdoor 2121
ANL 23
[Absolute Humidity] Outdoor 2123
INT 1
[ BMS ] Activation of the control by a computer
or an automat - mode BMS is activated if this
value is different from zero, This value is
decreased every second
3932
INT 2
[Room SP] Required room minimum fresh air
rate in % Middle of the dead zone.
3312
(BMS)
[Clock] Minute 3122
INT 5
[Clock] Day of the month 3123
INT 6
[Clock] Month 3124
INT 17
[Alarm] Code Error 1000
INT 18
[% of opening] Damper of fresh air 2413
INT 19
[% of opening] Valve gas 2618
INT 20
[% of opening] Electrical heaters (Triac) 2627
INT 21
[% of opening] Hot water coil 2633
DGT 1
[On / Off] Unit 3111
DGT 2
[Reset] Discharges the safety measures of the
unit
3112
DGT 3
[BMS] Activation of the Unoccupied mode [Off]
Occupied mode - [On] Unoccupied mode
3933
DGT 4
[Clock] [OFF] read hour & minute [ON] write
hour & minute
…
DGT 17