V2.2
-00
45
FAN CIRCUIT BREAKERS TRIPPED
Logical variable : DELECV
Incident codes KP02 : 90
KP07 icon :
Description
One or more thermomagnetic circuit breakers protecting the air condenser fans are tripped. (ELECV = 0).
Action
F The fault is displayed on the screen.
F The remote fault report is delayed for 6 minutes.
Resetting
The fault is reset automatically once all the fan circuit breakers are reset.
Trouble-shooting Solution
Bad connection or connections too tight.
Circuit breakers wrongly set.
Check connections.
Set protections according to the rated current for fans.