550 850 1600 2250
400 650 1225 1725
350 475 1075 1500
300 450 925 1300
225 325 700 1000
EAC / EAR 0251SM EAC / EAR 0291SM EAC / EAR 0351SM
l/s 0,88 0,99 1,06 1,22 1,37 1,03 1,16 1,24 1,43 1,61 1,22 1,38 1,53 1,70 1,91
m
3
/h 3,16 3,56 3,80 4,40 4,95 3,72 4,18 4,45 5,16 5,81 4,40 4,95 5,50 6,12 6,88
kPa 175 152 131 110 87 153 129 106 83 55 214 182 150 115 72
EAC / EAR 0431SM EAC / EAR 0472SM EAC / EAR 0552SM
l/s 1,47 1,66 1,80 2,04 1,68 1,89 2,11 2,34 2,63 1,96 2,21 2,42 2,73 3,07
m
3
/h 5,30 5,96 6,47 7,36 6,05 6,81 7,59 8,41 9,46 7,07 7,96 8,72 9,82 11,05
kPa 161 132 96 47 156 141 128 115 101 140 128 115 99 78
EAC / EAR 0672SM EAC / EAR 0812SM EAC / EAR 1003SM
l/s 2,39 2,69 3,03 3,32 3,73 2,89 3,25 3,60 4,01 3,44 3,87 4,21 4,78 5,38
m
3
/h 8,60 9,68 10,90 11,94 13,44 10,39 11,69 12,98 14,43 12,38 13,93 15,17 17,20 19,35
kPa 223 194 165 134 97 180 147 107 54 214 202 189 173 151
EAC / EAR 1103SM EAC / EAR 1203SM EAC / EAR 1303SM
l/s 3,86 4,34 4,89 5,36 6,03 4,38 4,92 5,34 6,08 6,84 4,85 5,46 6,01 6,74 7,58
m
3
/h 13,90 15,63 17,61 19,30 21,72 15,76 17,72 19,23 21,88 24,62 17,48 19,66 21,62 24,27 27,31
kPa 200 186 172 155 132 185 169 151 130 102 171 152 131 106 71
EAC / EAR 1403SM EAC / EAR 1604SM EAC / EAR 1804SM
l/s 5,24 5,90 6,63 7,27 8,19 5,85 6,58 7,13 8,12 9,14 6,88 7,74 8,31 9,55 10,75
m
3
/h 18,86 21,22 23,87 26,17 29,48 21,06 23,69 25,66 29,22 32,90 24,77 27,86 29,93 34,37 38,70
kPa 165 142 115 90 51 158 138 115 85 53 197 176 137 106 60
12
1.5.- HYDRAULIC SYSTEM DATA
1.- GENERAL CHARACTERISTICS
WATER FLOW AND AVAILABLE STATIC PRESSURE ( Factory supplied; standard water pump and lter).
NOTE: The ow data indicated in table are between a minimum and a maximum water ow.
With the twin pumps kit, the available static pressure will decrease 5% from the data shown above.
Unit conversion: Pressure 1KPa = 1/9,8 m.c.a. = 0,01 bar
1 bar = 10 m.c.a. = 100 kPa
MINIMUM WATER FLOW
The installation must never operate with less than the minimum water ow (see table above), this will cause:
i. - Freezing the water heat exchanger.
ii. - Contamination of the heat exchanger.
MAXIMUM WATER FLOW
See maximum water ow, (see table above). Always assure the minimum ∆T to the exchanger of 3ºC.
MAXIMUM WATER VOLUME IN THE INSTALLATION
The units with Hydronic or Hydraulic module include a expansion vessel.
The table below details the maximum water volume in the system.
If the water volume in the system is greater than that detailed in the table it will be necessary to add additional expansion
vessel(s). The system design must allow for water expansion and contraction.
MODELS
0251SM
to
0431SM
0472SM
to
0812SM
1003SM
to
1403SM
1604SM
1804SM
SOLUTION Water volume in liters
WATER
WATER + 10% GYT
WATER + 20% GYT
WATER + 30% GYT
WATER + 35% GYT
MODELS
Water ow
Available static pressure
MODELS
Water ow
Available static pressure
MODELS
Water ow
Available static pressure
MODELS
Water ow
Available static pressure
MODELS
Water ow
Available static pressure
Nominal conditions