TYPICAL UNIT CONTROL WIRE CONNECTIONS
5
WIRE RUN LENGTH AWG# INSULATION TYPE
LESS THAN 100’ (30M) 18 TEMPERATURE RATING
MORE THAN 100’ (30M) 16 35°C MINIMUM
A
RUN CONTROL WIRES THROUGH RIGHT CUTOUT.
B RUN CONTROL WIRES THROUGH WIRE TIES.
MAKE CONTROL WIRE CONNECTIONS USING FIELD
PROVIDED WIRE NUTS. SEE FIGURE 3 FOR CONNECTION
REQUIREMENTS.
C
D
TIGHTEN WIRE TIE TO SECURE 24VDC CONTROL WIRING.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL
WIRING) GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND
MAINTAINS SEPARATION OF FIELD INSTALLED LOW AND HIGH VOLTAGE
CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE
CONTROL BOX.