Purgetheairfromthechargehose.
Openthevalveatthebottomofthecylinderandpress
thecheckvalveonthechargesettopurgetheair(be
carefuloftheliquidrefrigerant).
Placethechargingcylinderontotheelectronicscale
andrecordtheweight.
Turnontheairconditionerincoolingmode.
Openthevalves(Lowside)onthechargesetand
chargethesystemwithliquidrefrigerant.
Whentheelectronicscaledisplaystheproperweight
(refertothegaugeandthepressureofthelowside),
disconnectthechargehosefromthethree-wayvalve’s
serviceportimmediatelyandturnofftheairconditioner
beforedisconnectingthehose.
Mountthevalvestemcapsandtheserviceport.Use
torquewrenchtotightentheserviceportcaptoa
torqueof18N.m(13.27ft·lbs).
Besuretocheckforgasleaks.
13.6. Servicing Indoor Unit Refrigeration
Circuit
13.6.1. Collecting Refrigerant into Outdoor Unit
Conrmthatboththetwo-wayandthree-wayvalves
aresettotheopenedposition
Removethevalvestemcapsandconrmthatthevalve
stemsareintheopenedposition.
Besuretouseahexagonalwrenchtooperatethe
valvestems.
Connectthechargehosewiththepushpinofhandlelo
tothethree-wayvalvesgasserviceport.
Airpurgingofthechargehose-OpenthehandleLo
valveofthemanifoldvalveslightlytopurgeairfromthe
chargehoseforvesecondsandthencloseitquickly.
Setthetwo-wayvalvetothecloseposition.
Operatetheairconditioneratthecoolingcycleand
stopitwhenthegaugeindicates0.1MPa(14psi).
Setthethree-wayvalvetotheclosedposition
immediately
Dothisquicklysothatthegaugeendsupindicating0.3
to0.5Mpa(43-72psi).
Disconnectthechargeset,andtightenthetwo-way
andthree-wayvalve’sstemnuts.
Useatorquewrenchtotightenthethree-wayvalves
serviceportcaptoatorqueof18N.m.
Besuretocheckforgasleakage.
13.6.2. Air Purging with Vacuum Pump
Completelytightenthearenutsoftheindoorand
outdoorunits,conrmthatboththetwo-wayandthree-
wayvalvesaresettotheclosedposition.
Connectthechargehosewiththepushpinofhandlelo
tothethree-wayvalvesgasserviceport.
Connectthechargehoseofhandlehiconnectiontothe
vacuumpump.
FullyopenthehandleLoofthemanifoldvalve.
Operatethevacuumpumptoevacuate.
Makeevacuationfor30minutesandcheckwhetherthe
compoundmeterindicates-0.1Mpa(500microns).If
themeterdoesnotindicate-0.1Mpa(500microbars)
afterpumping30minutes,itshouldbepumped20
minutesmore.Ifthepressurecan’tachieve-0.1Mpa
(500microbars)afterpumping50minutes,please
checkiftherearesomeleakagepoints.
FullyclosethehandleLovalveofthemanifoldvalve
andstoptheoperationofthevacuumpump.Conrm
thatthegaugeneedledoesnotmove(approximately
veminutesafterturningoffthevacuumpump).
Turnthearenutofthethree-wayvalvesabout45°
counterclockwiseforsixorsevensecondsafterthegas
comingout,thentightenthearenutagain.Makesure
thepressuredisplayinthepressureindicatorisalittle
higherthantheatmospherepressure.Thenremovethe
chargehosefromthethree-wayvalve.
Fullyopenthetwo-wayvalveandthree-wayvalveand
securelytightenthecapofthethree-way
13.7. Evacuation after Servicing the Outdoor
Unit Refrigeration Circuit
13.7.1. Evacuation of the Complete Refrigeration
Circuit, Indoor and Outdoor Unit
Conrmthatboththetwo-wayandthree-wayvalves
aresettotheopenedposition.
Connectthevacuumpumptothree-wayvalve’sservice
port.
Evacuationforapproximatelyonehour.Conrmthat
thecompoundmeterindicates-0.1Mpa(500Microns/
29.9in.hg).
Closethevalve(Lowside)onthechargeset,turnoff
thevacuumpump,andconrmthatthegaugeneedle
doesnotmove(approximately5minutesafterturning
offthevacuumpump).
Disconnectthechargehosefromthevacuumpump.