MCC_AGU/0102-G • 17 •
SCHALLDRUCKPEGEL
NOISE LEVELS
Spektrum pro Oktave (dBA) Allgemeine
Spectrum per octave band (dBA) Lautstärke
Global
sound power
MCC 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
71 S 50 62 70 76 76 79 72 66 83
81 S 52 64 73 78 78 80 74 68 85
92 S 61 73 81 86 86 85 80 73 91
102 S 70 81 90 94 95 93 89 81 100
132 S 70 81 90 94 95 93 89 82 100
162 S 65 77 85 90 91 89 84 77 96
192 P 72 83 92 96 97 95 91 84 102
212 P 71 82 91 95 96 94 91 84 101
242 P 71 8 919596949185 101
282 P 73 84 93 97 98 96 93 87 103
302 P 74 85 94 98 99 97 93 86 104
322 P 74 85 94 98 99 97 93 86 104
Allgemeiner Schalldruckpegel gemessen gemäß ISO-Norm 3744 im Rahmen des Eurovent-Zertifizierungsprogramms.
Global sound power level measured in compliance with ISO standard 3744 and under Eurovent certification programm
Schalldruck in dB(A) gemessen in 10 m Entfernung, in einem freien Feld auf einer reflektierenden Oberfläche. Es handelt sich nur um einen
Richtwert.
Zur Ermittlung der Schalldruckeigenschaften am Aufstellungsort werden nur die Werte des Lautstärkespektrums und der globalen
Lautstärke herangezogen.
Sound pressure in dB(A) calculated at 10 m, in a free field on a reflecting surface, is given as a guide only.
Only the sound power spectrum and the global sound power value are used in determining pressure characteristics on site.
Spektrum pro Oktave (dBA) Allgemeine
Spectrum per octave band (dBA) Lautstärke
Global
sound power
MCC 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz dBA
71 S 44 55 65 70 69 78 70 64 80
81 S 46 57 67 71 71 79 71 65 81
92 S 55 66 75 77 73 78 71 59 82
102 S 64 75 84 85 78 81 75 67 89
132 S 64 75 84 85 78 82 76 68 89
162 S 59 70 79 80 76 82 75 69 87
192 P 66 77 86 87 84 82 79 75 92
212 P 65 76 85 86 84 83 85 79 92
242 P 65 76 85 86 84 84 87 82 93
282 P 67 78 87 88 84 84 88 83 94
302 P 68 79 88 88 88 86 80 71 94
322 P 68 79 88 89 87 85 82 74 94
Schalldruckpegel außerhalb der Maschine (Ventilatorausblas mit isoliertem Kanal)
Noise levels outside the unit (fan discharge with insulated ducting)
Schalldruckpegel im Luftkanal
Noise level in the air duct
STANDARDMASCHINE (100 Pa verfügbarer Druck)
STANDARD UNIT (100 Pa available pressure)

Other manuals for Lennox MCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCC Series and is the answer not in the manual?

Lennox MCC Series Specifications

General IconGeneral
BrandLennox
ModelMCC Series
CategoryChiller
LanguageEnglish

Related product manuals