Page 6
I-UNIT COMPONENTS
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
CAUTION
Electrostatic discharge can affect elec
tronic components. Take precautions
to neutralize electrostatic charge by
touching your hand and tools to metal
prior to handling the control.
ML196DFE unit components are shown in figure 1. The
combustion air inducer, gas valve and burners can be ac
cessed by removing the outer access panel. The blower
and control box can be accessed by removing the blow
er access panel.
A-Control Box Components (Figure 2)
Unit transformer (T1) and integrated ignition control (A92)
are located in the control box. In addition, a door interlock
switch (S51) is located in the control box.
FIGURE 2
DOOR INTERLOCK
SWITCH (S51)
INTEGRATED IGNITION
CONTROL
(A92)
TRANSFORMER
(T1)
ML196DFE Control
Box
CIRCUIT
BREAKER
(CB8)
1. Transformer (T1)
A transformer located in the control box provides power to
the low voltage section of the unit. The transformers on all
models are rated at 40VA with a 120V primary and 24V
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 120VAC is located on
the control box. The switch is wired in series with line volt
age. When the blower door is removed the unit will shut
down.
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The
switch provides overcurrent protection to the transformer
(T1). The breaker is rated at 3A at 32V. If the current ex
ceeds this limit the breaker will trip and all unit operation will
shutdown. The breaker can be manually reset by pressing
the button on the face.
4. Integrated Ignition Control (A92)
WARNING
Shock hazard.
Disconnect power before servicing. Control is not
field repairable. If control is inoperable, simply re
place entire control.
Can cause injury or death. Unsafe operation will
result if repair is attempted.
The hot surface ignition control system consisting of an in
tegrated control (figure 3 with control terminal designa
tions in tables 1, 2 and 3), sensor and ignitor (figure 5). The
integrated control and ignitor work in combination to en
sure furnace ignition and ignitor durability. The integrated
control, controls all major furnace operations. The inte
grated control also features a RED LED for troubleshoot
ing and two accessory terminals rated at (1) one amp. See
table 4 for troubleshooting diagnostic codes. The nitride
ignitor is made from a non-porous, high strength propri
etary ceramic material that provides long life and trouble
free maintenance.
TABLE 1
4-Pin Terminal Designation
PIN # FUNCTION
1 Combustion Air Inducer Line
2
Ignitor Line
3
Combustion Air Inducer Neutral
4
Ignitor Neutral
TABLE 2
12-Pin Terminal Designations
PIN # FUNCTION
1 High Limit Output
2 Not Used
3 24V Line
4 Not Used
5 Rollout Switch Out
6 24V Neutral
7 High Limit Input
8 Ground
9 Gas Valve Common
10 Pressure Switch In
11 Rollout Switch In
12 Gas Valve Out