1.8. MPAMulti-ZoneSpecicationsOutdoorUnits(3-4Ton)
Nominal Size - Tons 3 4
Outdoor Unit Model No. MPA036S4M MPA048S4M
Number of Zones Up to 4 Up to 5
1
AHRI Ratings SystemType Ducted Non-Ducted Ducted Non-Ducted
Cooling-Btuh 34,000 36,000 42,000 42,000
HighTemperatureHeating-Btuh 36,000 36,000 51,000 49,000
LowTemperatureHeating-Btuh 24,400 23,400 31,800 31,200
SEER 15.00 18.00 18.00 20.00
EER 8.20 8.80 11.00 12.50
HSPF(RegionIV) 9.3 10.0 9.5 10.0
AHRIReferenceNumber 8129615 8129614 8129617 8129616
Energy Star No No No Yes
Ambient Temperature Range - °F Cooling 5 - 122 5 - 122
Heating –13 - 76 –13 - 76
Sound Data (dBA) Cooling 62 58
Heating 64 62
Refrigerant Chargefurnished(R-410A) 7lbs.15oz. 9lbs.8oz.
Maximumlinelengthwithfurnishedcharge(perzone)-ft. 25 25
Additionalchargerequiredperft.-oz. 0.161 0.161
Compressor No.andType Twin-Rotary Twin-Rotary
Refrigerantoiltype FV50S FV50S
Refrigerantoilcharge-oz. 36.2 47.3
Connections - in. Liquid+Gas+Gaspipe(are) (4)1/4+(3)3/8+(1)1/2 (5)1/4+(3)3/8+(2)1/2
Maximumlengthforallrooms-ft. 197 246
Maximumlengthforoneindoorunit-ft. 98 98
Maximumheight
differencebetween
indoor unit and outdoor
unit
Outdoorunitabovethanindoor
unit - ft.
33 33
Outdoorunitbelowthanindoor
unit - ft.
49 49
Maximumdifferenceinlevelbetweenindoorunits-ft. 33 33
Outdoor
Fan
(No.)Diameter-in. (1) - 22 (2) - 20
Totalairvolume-cfm 2240 (2)4240
rpm 950 (2) 800
Outdoor Coil Numberofrows 2.6 2
Finsperinch 15 15
Fintype Hydrophilicaluminium
Tubeoutsidediameter-in. 5/16 5/16
Tubetype Riedcoppertubing
Net face area - ft.
2
6.42 14.33
Design Pressure PSIG 550/340 550/340
Shipping Data Net/Shippingweight(lbs.) 162/174 218/245
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase 208/230V 208/230V
2
MaximumOvercurrentProtection(amps) 45 50
3
Minimum circuit ampacity 30 35
CompressorRatedloadamps 19.5 22
Outdoor Fan Motor Ratedloadamps 1.30 (2) 0.9
Output-W 120 (2) 85
NOTE-PerAHRI,thecertiedratingsforsystemsarevalidforallcombinationsofindoorunitswiththespecicoutdoorunitslistedaboveandintheAHRIDirectoryof
CertiedEquipment.Pleasevisithttp://www.ahridirectory.orgforfurtherdetailsandlatestupdates.
1
RatingsareAHRIcertiedtoAHRIStandard210/240-2008;
•CoolingRatings-80°Fdrybulb/67°Fwetbulbenteringindoorcoilairand95°Fdrybulb/75°Fwetbulboutdoorairtemperature.
•HighTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand47°Fdrybulb/43°Fwetbulboutdoorairtemperature.
•LowTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand17°Fdrybulb/15°Fwetbulboutdoorairtemperature.
NOTE-Extremesofoperatingrangeareplusandminus10%oflinevoltage.
2
HACRtypecircuitbreakerorfuse.
3
RefertoNationalorCanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
NOTE-Adaptorsarefurnishedforthegaspipeconnections:
036 - (3) 3/8 x 1/2 in. and (1) 1/2 x 3/8 in.