EasyManuals Logo
Home>Lennox>Air Conditioner>MLA030S4M

Lennox MLA030S4M Service Manual

Lennox MLA030S4M
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #128 background imageLoading...
Page #128 background image
128
25. Troubleshooting Indoor Unit Error Codes
Error Code: CP
Description: MWMA models only.
General Note: None.
This S4 jumper is on the adapter
board. There needs to be a
jumper in place . If jumper is
there then make sure it is making
good contact.
Adapter board
located on door
of MWMA unit
The unit will show “CP” if the cap
missing or not making contact.
Need to make sure the two pin to
making contact with the jumper.
The Cap
Adapter board
Error Code: E0
Description: IndoorUnitEEPROMmalfunction.
General Note: PCBmainchipdoesnotreceivefeedbackfromEEPROMchip.
E0
Shutoffthepowersupplyandturniton1min-
utelater.Isitstilldisplayingtheerrorcode?
IftheEEPROMchipissolderedonPCB,re-
placethePCB.Otherwise,checkwhetherthe
EEPROMchipispluggedinPCBproperly?
Yes
Yes
InserttheEEPROMproperly
No
ReplacetheindoorPCB.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MLA030S4M and is the answer not in the manual?

Lennox MLA030S4M Specifications

General IconGeneral
BrandLennox
ModelMLA030S4M
CategoryAir Conditioner
LanguageEnglish

Related product manuals