EasyManuals Logo
Home>Lennox>Air Conditioner>MMDA048S4-1P

Lennox MMDA048S4-1P User Manual

Lennox MMDA048S4-1P
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #131 background imageLoading...
Page #131 background image
Lennox Mini-Split Service Manual / Page 131
Multi-Zone Outdoor Units Quick Reference
DISPLAY
OUTDOOR UNIT ERROR CODE DEFINITION
Outdoor EEPROM error
E0
Communication error between outdoor unit and all indoor units
E2
Communication error between outdoor unit main control
and IPM control
E3
Temp. sensor error (outdoor coil sensor, outdoor ambient sensor,
compressor discharge sensor, indoor unit coil outlet temp. sensor)
E4
High or Low voltage protection
E5
Outdoor DC fan speed error
E8
F1
Indoor unit #1 coil outlet temp. sensor error
F2
Indoor unit #2 coil outlet temp. sensor error
F3
Indoor unit #3 coil outlet temp. sensor error
F4
Indoor unit #4 coil outlet temp. sensor error
F5
F6
Indoor unit #5 coil outlet temp. sensor error
Indoor unit #6 coil outlet temp. sensor error
P1
High pressure switch open
P2
Low pressure switch open
P3
Outdoor Compressor current overload sensed
P4
High temperature sensed at compressor discharge line
P5
High temperature sensed at outdoor coil
P6
Inverter module (IPM) error
Outdoor Unit Sticker Shown - See Indoor Unit for Additional Error Code Information

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MMDA048S4-1P and is the answer not in the manual?

Lennox MMDA048S4-1P Specifications

General IconGeneral
BrandLennox
ModelMMDA048S4-1P
CategoryAir Conditioner
LanguageEnglish

Related product manuals