EasyManuals Logo
Home>Lennox>Air Conditioner>MPB018S4M-*P

Lennox MPB018S4M-*P User Manual

Lennox MPB018S4M-*P
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11
1.7. MPAMulti-ZoneSpecicationsOutdoorUnits(1.5-2.5Ton)
Nominal Size - Tons 1.5 2.5
Outdoor Unit Model No. MPA018S4M MPA030S4M
Number of Zones 2 Up to 3
1
AHRI Ratings SystemType Ducted Non-Ducted Ducted Non-Ducted
Cooling-Btuh 17,000 18,000 27,000 25,000
HighTemperatureHeating-Btuh 18,000 18,500 32,000 32,000
LowTemperatureHeating-Btuh 10,900 11,000 20,000 20,000
SEER 18.00 21.00 16.50 22.00
EER 12.50 12.50 9.50 12.50
HSPF(RegionIV) 8.5 9.6 8.8 9.6
AHRIReferenceNumber 8129621 8129607 8129624 8129613
Energy Star Yes Yes No Yes
Ambient Temperature Range - °F Cooling 5 - 122 5 - 122
Heating –13 - 76 –13 - 76
Sound Data (dBA) Cooling 57 59
Heating 62 62
Refrigerant Chargefurnished(R-410A) 4lbs.4oz. 6lbs.3oz.
Maximumlinelengthwithfurnishedcharge(perzone)-ft. 25 25
Additionalchargerequiredperft.-oz. 0.161 0.161
Compressor No.andType Twin-Rotary Twin-Rotary
Refrigerantoiltype ESTEROILVG74 ESTEROILVG74
Refrigerantoilcharge-oz. 16.9 27.7
Connections - in. Liquid+Gaspipe(are) (2)1/4+(2)3/8 (3)1/4+(3)3/8
Maximumlengthforallrooms-ft. 98 148
Maximumlengthforoneindoorunit-ft. 66 82
Maximumheight
differencebetween
indoor unit and outdoor
unit
OutdoorunitABOVE
indoor unit - ft.
33 33
OutdoorunitBELOW
indoor unit - ft.
49 49
Maximumdifferenceinlevelbetweenindoorunits-ft. 33 33
Outdoor
Fan
(No.)Diameter-in. (1) - 18 (1) - 22
Totalairvolume-cfm 1470 2060
rpm 750 850
Outdoor Coil Numberofrows 2 1.6
Finsperinch 14 15
Fintype Hydrophilicaluminium
Tubeoutsidediameter-in. 3/8 3/8
Tubetype Riedcoppertubing
Net face area - ft.
2
4.9 6.42
Design Pressure PSIG 550/340 550/340
Shipping Data Net/Shippingweight(lbs.) 106 / 115 144/155
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase 208/230V 208/230V
2
MaximumOvercurrentProtection(amps) 20 25
3
Minimum circuit ampacity 18 20
CompressorRatedloadamps 10 12
Outdoor Fan Motor Ratedloadamps 0.74 0.90
Output-W 50 120
NOTE-PerAHRI,thecertiedratingsforsystemsarevalidforallcombinationsofindoorunitswiththespecicoutdoorunitslistedaboveandintheAHRIDirectoryof
CertiedEquipment.Pleasevisithttp://www.ahridirectory.orgforfurtherdetailsandlatestupdates.
1
RatingsareAHRIcertiedtoAHRIStandard210/240-2008;
•CoolingRatings-80°Fdrybulb/67°Fwetbulbenteringindoorcoilairand95°Fdrybulb/75°Fwetbulboutdoorairtemperature.
•HighTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand47°Fdrybulb/43°Fwetbulboutdoorairtemperature.
•LowTemperatureHeatingRatings-70°Fdrybulb/60°Fwetbulbenteringindoorcoilairand17°Fdrybulb/15°Fwetbulboutdoorairtemperature.
NOTE-Extremesofoperatingrangeareplusandminus10%oflinevoltage.
2
HACRtypecircuitbreakerorfuse.
3
RefertoNationalorCanadianElectricalCodemanualtodeterminewire,fuseanddisconnectsizerequirements.
NOTE-Adaptorsarefurnishedforthegaspipeconnections:
018 - (2) 3/8 x 1/2 in.
030 - (3) 3/8 x 1/2 in.

Table of Contents

Other manuals for Lennox MPB018S4M-*P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MPB018S4M-*P and is the answer not in the manual?

Lennox MPB018S4M-*P Specifications

General IconGeneral
BrandLennox
ModelMPB018S4M-*P
CategoryAir Conditioner
LanguageEnglish