93
Table 3. Status Indicators
Display Remark
47 IndoorunitFcapacitydemandcode Not used
48 IndoorunitFevaporatoroutlettemp.(T2BF) Not used
49 IndoorunitFroomtemp.(T1F) Not used
50 IndoorunitFevaporatortemp.(T2F) Not used
51 EXVopenangleforFindoorunit Not used
19.4. Outdoor Unit Digital Display Tube
ThereisadigitaldisplaytubeinoutdoorPCB.Digitaldisplaytubedisplayfunction
Table 4. Operation Display
Description
Instandby,theLEDdisplays“--”
Incompressoroperation,theLEDdisplaytherunningfrequency,
Indefrostingmode,TheLEDdisplays“dF”oralternativedisplaysbetweenrunningfrequencyand“dF”(eachdisplays0.5s)
Incompressorpre-heating,TheLEDdisplays“PH”oralternativedisplaysbetweenrunningfrequencyand“PH”(eachdisplays0.5s)
Duringtheoilreturnprocess,TheLEDdisplays“RO”oralternativedisplaysbetweenrunningfrequencyand“RO”(eachdisplays0.5s)
Inlowambientcoolingmode,theLEDdisplays“LC”oralternativedisplaysbetweenrunningfrequencyand“LC”(eachdisplays0.5s)
Inforcedcoolingmode,theLEDdisplays“FC”oralternativedisplaysbetweenrunningfrequencyand“FC”(eachdisplays0.5s)
WhenPFCmoduleprotectionoccursthreetimeswithin15minutes,theLEDdisplays“E6”oralternativedisplaysbetweenrunningfrequencyand
“E6”(eachdisplays0.5s)
Inprotectionormalfunction,theLEDdisplayserrorcodeorprotectioncode.
19.5. Dry Mode Operation - MWMA and MWMB
19.5.1. Procedure
1. PresstheMODE button to select DRY mode.
2. PresstheUP/ DOWNbuttontoselectthedesiredtemperature.Thetemperaturesettingrangeisfrom62°Fto86°Fin
one degree increments.
NOTE: The blower is preset at a low speed and cannot be changed therefore it will get cold and most likely will over
shoot the temperature setting by 6-10 degrees depending on the room size or other various factors. Also the
Follow Me mode does not operate in this mode. The Follow Me mode is only available when a return air sensor
is utilized. Typically in most cases the Follow Me mode will not be sufcient to remove excessive humidity.
Inaddition,theoutdoorunitsdonothaveahumidistatinstalledthereforetheyareunabletodeterminehumidity
levels.Thisproductisnotrecommendasamainsourcefordehumidication.
19.5.2. Dry Mode Operation Sequence
Whenindrymodeoperationtheunitisactuallyincoolingmodewithalowspeedbloweroperation.Thecompressorwillstop
whentheroomtemperatureistwodegreesCelsiuslowerthanthetemperaturesetting.
HoweverthereisatemperaturecompensationforcoolingmodethatistwodegreesCelsius.Sotheunitwillstopwhenthe
temperatureisfourdegreesCelsiuslowerthantheroomtemperaturesettings.
NOTE: Four degrees Celsius is equivalent to 8°F difference.
19.6. Test Run - MWDA and MWMB
Onlyperformtestrunafteryouhavecompletedthefollowingsteps:
• ElectricalSafetyChecks–Conrmthattheunit’selectricalsystemissafeandoperatingproperly
• GasLeakChecks–Checkallarenutconnectionsandconrmthatthesystemisnotleaking
• Conrmthatgasandliquid(highandlowpressure)valvesarefullyopen.