9.2. MPC Single-Zone Specications (0.75 - 1.5 Ton)
Nominal Size - Tons 0.75 1 1.5
Outdoor Unit Model No. MPC009S4S MPC012S4S-1L
MPC012S4S-1P
MPC018S4S
Ambient Temperature Operating
Range - °F
Cooling –13 - 122 –13 - 122 –13 - 122
Heating –13 - 86 –13 - 86 –13 - 86
Energy Star Yes Yes Yes
Sound Data (dBA) Cooling/Heating (115V) - - - 54 - - -
Cooling/Heating (208/230V) 53 53.5 58
Refrigerant
(R-410A)
Charge furnished (115V) - - - 2 lbs. 8 oz. - - -
Charge furnished (208/230V) 2 lbs. 6 oz. 2 lbs. 6 oz. 3 lbs. 8 oz.
Maximum line length with furnished charge - ft. 15 15 15
Additional charge required per ft. - oz. 0.16 0.16 0.16
Compressor No. and Type (1) Rotary (1) Rotary (1) Rotary
Refrigerant oil type Ester Oil VG74 Ester Oil VG74 Ester Oil VG74
Refrigerant oil charge - oz. 10.5 10.5 14.9
Connections - in. Liquid/Gas pipe (are) 1/4 / 3/8 1/4 / 1/2 1/4 / 1/2
Maximum refrigerant pipe length - ft. 82 82 98
Max. difference in level of indoor unit - ft. 33 33 66
Outdoor
Fan
(No.) Diameter - in. 16-1/2 16-1/2 16-1/2
Total air volume - cfm 1295 1295 1765
rpm 800 800 810
Outdoor Coil Number of rows 2 2 3
Fins per inch 21 21 19
Fin type Hydrophilic aluminum
Tube outside diameter - in. 5/16 5/16 5/16
Tube type Ried copper tubing
Net face area - ft.
2
4.04 4.04 5.90
Application area - sq. ft. 130 - 195 170 - 250 260 - 375
Design Pressure PSIG 550/340 550/340 550/340
Shipping
Data
Net/Shipping weight (lbs.) (115V) 64 / 69 67 / 72 95 / 102
(208/230V) 64 / 69 64 / 69 95 / 102
ELECTRICAL DATA
Electrical Characteristics - 60 Hz - 1 Phase 208/230V 115V 208/230V 208/230V
1
Maximum Over-current Protection (amps) 15 25 15 25
2
Minimum circuit ampacity 13 19 13 17
Compressor Rated load amps 6.4 6.4 6.4 12
Outdoor Fan Motor Rated load amps 0.4 0.6 0.4 0.76
Output - W 34 34 34 80
NOTE - Extremes of operating range are plus and minus 10% of line voltage.
1
HACR type circuit breaker or fuse.
2
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.