XC21 - 2 to 5 Ton Air Conditioner / Page 11
OUTDOOR SOUND DATA
1
Unit
Model No.
Octave Band Sound Power Levels dBA, re 10
-12
Watts
1
Sound
Rating
Number
(dB)
Center Frequency - HZ
63 125 250 500 1000 2000 4000 8000
XC21-024 48.5 54.5 61 64 62 60 56 49 69
XC21-036 49 60 65 66.5 64.5 61.5 56.5 50 71
XC21-048 49.5 59.5 66.5 68 67 63 58 52 73
XC21-060 50 60 65.5 70 68.5 64 57 50.5 73
NOTE - the octave sound power data does not include tonal correction.
1
Tested according to AHRI Standard 270-2008 test conditions.
See
Notes
See
Notes
See
Notes
See
Notes
Service
INSTALLATION CLEARANCES - INCHES (MM)
NOTES -
One of these three sides must be 36 in. (914 mm).
One of the two remaining sides may be 12 in. (305 mm).
The remaining side may be 6 in. (152 mm).
Service Clearance − 30 in. (762 mm)
48 in. (1219 mm) clearance required on top of unit
24 in. (610 mm) required between two units
FIELD WIRING
B
DISCONNECT
SWITCH
(By Others)
LENNOX
AIR
CONDITIONER
LENNOX
HEATING UNIT
OR
AIR HANDLER
UNIT
DISCONNECT
SWITCH
(By Others)
THERMOSTAT
(Optional)
C
D
A
A - Two Wire Power (not furnished)
B - Two Power (not furnished) See Electrical Data
C - Four Wire Low Voltage (not furnished) 18 ga. minimum
D - Six Wire Low Voltage (not furnished) 18 ga. minimum
All wiring must conform to NEC or CEC and local electrical codes.