34
6.3. RFI filter
For radio interference suppression according to EN 55011, limit
value class A or B.
Assigned RFI filters for mains voltage of 400 V
Supply module type 9212 9215 9217
Mains current RFI filter
8 A 25 A 50 A
Order no. mains filter
EZF3_008A001 EZF3_025A001 EZF3_050A004
Filter for mains voltages of up to 460 V: please contact
manufacturer
6.4. External fuses
Semiconductor protection
External fast acting fuses in the mains input protect the input
rectifier in the supply module.
Recommended semiconductor protection fuses (at mains side):
Supply module 9212 9215 9217
Mains input with
rectifier protection
FF
20A / 700V
14 x 51
FF
63A / 700V
22 x 58
FF
100A / 700V
22 x 58
Order no.
EFSFF0200ARH EFSFF0630ARI EFSFF1000ARI
Input cables must be protected with standard fuses adapted to the
cross-sectional area of the cables.
6.5. System cables
Note
For best interference immunity results, cut the cables to the required length.
6.5.1. System cables for control terminal block X5
Design for left X5 terminals right X5 terminals
Order no.
EW00340899 EW00340898
Fehler! Es
ist nicht
möglich,
durch die
Bbit

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze 9200 Series and is the answer not in the manual?

Lenze 9200 Series Specifications

General IconGeneral
BrandLenze
Model9200 Series
CategoryController
LanguageEnglish

Related product manuals