13
Electrical installaon
Operang instrucons I510-Cabinet
5.7 Three-phasemainsconnecon400V
Terminaldata,3-phase400V
I51AExxxF I51BExxxF I51AExxxF I51AExxxF I51AExxxF I51AExxxF I51AxxxF I51AxxxF I51AxxxF
Inverter [kW] 0.37 ... 2.2 3 ... 4 3 ... 5.5 7.5 ... 11 0.37 ... 5.5 7.5 ... 11 0.37 ... 2.2 3 ... 5.5 7.5 ... 11
Connecon Mains connecon X100 PE connecon Motor connecon X105
Connecon type Pluggable
screw terminal
Pluggable
screw terminal
Screw terminal PE screw Pluggable
screw terminal
Screw terminal
Min. cable cross-secon mm² 1 1.5 1
Max. cable cross-secon mm² 2.5 2.5 6 16 6 16 2.5 6 16
Stripping length mm 8 8 9 11 10 11 8 9 11
Tightening torque Nm 0.5 0.5 0.5 1.2 2 3.4 0.5 0.5 1.2
Tools required 0.5 x 3.0 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0 Torx 20 PZ2 0.5 x 3.0 0.6 x 3.5 0.8 x 4.0
Fusingdata/performancedata
Inverter [kW] 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15
Rated output current
(heavy duty)
A 1.3 1.8 2.4 3.2 3.9 5.6 7.3 9.5 13 16.5 23.3 -
Max. Output current (15 s) A 2.6 3.6 4.8 6.4 7.8 11.2 14.6 19 26 33 47 -
Rated output current
(light duty)
A - - - - - - - 8.8 11.9 15.6 23 28.2
Max. Output current (15 s) A 14.6 19 26 33 47
Operaonwithoutmainschoke
Fuse
Characterisc gG/gL or gRL -
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 -
Circuit breaker
Characterisc B -
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 -
Operaonwithmainschoke
Fuse
Characterisc gG/gL or gRL
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 32
Circuit breaker
Characterisc B
Max. rated current A 10 10 10 16 16 16 25 25 25 32 32 32
Earth-leakage circuit breaker
3-phase mains connecon ≥ 30 mA, type B ≥ 300 mA, type B
A mains choke must be used for light duty loads over 15 kW.
Mainsconnecon
Valid for I51AExxxF inverter.
+UG
3/PE
AC 340 V ... 528 V
45 Hz ... 65 Hz
F1
…
F3
Q1
X100
L1
L2
L3
PE
N
L3
L2
3/N/PE
AC 400 V
-UG
Motorconnecon
X105
U
V
W
Rb1
Rb2
M
3~