22
Commissioning
Operang Instrucons i510-Cabinet
Display code Name
Possiblesengs/
value ranges
Keypad code Informaon
P440.02 AO1 funcon Output frequency [1] Actual output frequency (resoluon: 0.1 Hz).
Frequency setpoint [2] Actual frequency setpoint (resoluon: 0.1 Hz).
Analog input 1 [3] Input signal from analog input 1 (resoluon: 0.1 %).
P440.03 AO1 min. Signal -2147483648 ... 0 ...
2147483647
Denion of the signal value that corresponds to the minimum value at analog output 1.
P440.04 AO1 max. signal -2147483648 ... 1000 ...
2147483647
Denion of the signal value that corresponds to the maximum value at analog output 1.
P450.01 Freq. preset 1 0.0 ... 20.0 ... 599.0 Hz Parameterizable frequency setpoints (preset 1).
P450.02 Freq. preset 2 0.0 ... 40.0 ... 599.0 Hz Parameterizable frequency setpoints (preset 2).
P450.03 Freq. preset 3
0.0 ... 50.0 | 60.0 ... 599.0 Hz *
Parameterizable frequency setpoints (preset 3).
P450.04 Freq. preset 4 0.0 ... 0.0 ... 599.0 Hz Parameterizable frequency setpoints (preset 4).
Defaultseng=boldprint|*Defaultsengisdevice-dependent
7.4.2 Group2:Basicseng
Display code Name Possiblesengs Keypad code Informaon
P225.00 Quick stop decelera-
on me
1.0 s Quick stop deceleraon me for “MS: Velocity mode”
If the “Quick stop” funcon is acvated, the motor is brought to a standsll within the deceleraon me set here.
The set deceleraon me refers to the period of deceleraon from the set maximum frequency (P211.00) to standsll. In the case of a lower
actual frequency, the actual deceleraon me is reduced accordingly.
Seng is not eecve in operang mode P301.00 = “CiA:Velocity mode”.
7.4.3 Group 3: Motor control
Display code Name Possiblesengs Keypad code Informaon
P320.04 Rated torque 50 ... 50000 rpm General motor data.
Congure sengs as specied by the data on the motor nameplate.
Note!
Take the phase connecon implemented for the motor (star or delta conguraon) into account when entering the motor nameplate data. Only
enter data associated with the relevant conguraon.
P320.05 Rated frequency
1.0 ... 1000.0 Hz
P320.06 Rated power 0.00 ... 655.35 kW
P320.07 Rated voltage 0 ... 65535 V
P320.08 Cosine phi 0.00 ... 1.00
P327.04 Idenfy motor data 0 ... 1 1 = start automac idencaon of the motor data.
Inverter characteriscs, motor equivalent circuit data and controller sengs are idened and set automacally.
The motor is energized during the procedure!
P327.05 Calibrate motor data
(non-energized)
0 ... 1 1 = start automac calibraon of the motor data.
A default inverter characterisc is loaded.
The motor equivalent circuit data and controller sengs are calculated on the basis of the currently set rated motor data.
The motor is not energized.

Other manuals for Lenze i510 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i510 Series and is the answer not in the manual?

Lenze i510 Series Specifications

General IconGeneral
BrandLenze
Modeli510 Series
CategoryInverter
LanguageEnglish

Related product manuals