Operating instructions i550 motec frequency inverter | 18
© 03/2022 · EN · www.Lenze.com
Functional safety
DANGER!
Uncontrolled start-up
Improper installation of the safety engineering system can cause an uncontrolled starting
action of the drives.
Possible consequences: Death or severe injuries
Safety engineering systems may only be installed and commissioned by qualied personnel.
All wiring must be EMC-compliant.
All control components (switches, relays, PLC, ...) must comply with the requirements of EN
ISO13849-1 and EN ISO 13849-2.
Switches, relays with at least IP54 enclosure.
Devices with a degree of protection less than IP54 must always be installed in a control
cabinet with a minimum protection class of IP54.
The wiring must be shielded.
It is essential to use insulated wire end ferrules for wiring.
All safety-relevant cables outside the control cabinet must be protected, e.g. by means of a
cable duct.
Securely eliminate short-circuits and crossed wires according to the specications of
ENISO13849-2.
Please refer to EN ISO13849-1 and EN ISO 13849−2 for all further requirements and
measures.
In the case of an external force eect on the drive axes, additional brakes are necessary. In
particular, please observe the eect of gravitational force on hanging loads!
For safety-related braking functions, use safety-rated brakes only.
The user must ensure that the inverter is only operated within the specied environmental
conditions in its intended application. Only by doing so can the specied safety-related
characteristics be adhered to.
DANGER!
Automatic restart when the requirement of the safety function is disabled.
Possible consequences: Death or severe injuries
You must implement external measures in accordance with EN ISO 13849-1 to ensure that
the drive only starts up again after an acknowledgment.
NOTE
Overvoltage
Possible consequences: Destruction of the safety component
Make sure that the maximum voltage (maximum rated) at the safe inputs does not exceed
32 V DC.
NOTE
Excessive humidity or condensation
Possible consequences: Malfunction or irreparable damage to safety component
Only commission the safety component when it has acclimatized.
Electrical installation
3-phase | 480 V3-phase | 230/240V
3-phase | 400 V
Control connections
Connection diagram
Networks
Functional safety
Safe torque o (STO)
PTC input
Preparation

Other manuals for Lenze i550 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i550 Series and is the answer not in the manual?

Lenze i550 Series Specifications

General IconGeneral
BrandLenze
Modeli550 Series
CategoryInverter
LanguageEnglish

Related product manuals