EasyManuals Logo

Lenze L-force Drives 9400 Series User Manual

Lenze L-force Drives 9400 Series
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #83 background imageLoading...
Page #83 background image
Wiring the device
Important notes
5
83
EDK94SH366 ZH/EN 3.1
5 Wiring the device
5.1 Important notes
Danger!
All power terminals carry hazardous voltages up to 20 minutes after mains
disconnection.
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800−5−1. Especially:
Fixed installation
PE connection must conform to standards (PE conductor diameter
³ 10 mm
2
or PE conductor must be connected twice)
Stop!
The device contains components that can be destroyed by electrostatic
discharge!
Before working on the device, personnel must ensure that they are free of
electrostatic charge by using appropriate measures.
Stop!
No device protection in the event of too high mains voltages
The mains input is not fused internally.
Possible consequences:
ƒ Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ Observe the max. permissible mains voltage.
ƒ Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze L-force Drives 9400 Series and is the answer not in the manual?

Lenze L-force Drives 9400 Series Specifications

General IconGeneral
BrandLenze
ModelL-force Drives 9400 Series
CategoryServo Drives
LanguageEnglish

Related product manuals