EasyManuals Logo
Home>LG>Air Conditioner>Multi F MAX PMBD3640

LG Multi F MAX PMBD3640 User Manual

LG Multi F MAX PMBD3640
79 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
41
Refrigerant Piping Connections
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
MULTI
F
MAX
MULTI
F
Flushing the Refrigerant Piping
Flushing is a method of cleaning the refrigerant piping using pres-
surized nitrogen gas. Flushing:
1. Removes oxidation bubbles that may have formed inside the
copper piping if nitrogen replacement was insufficient during
soldering.
2. Removes foreign material and moisture from piping if the piping
wasn’t stored properly.
3. Checks connections in pipes linking outdoor and indoor units
(both liquid and gas pipes).
72.5 psi
Taping
Primary
Side
Pressure Regulator
Secondary Side (72.5 psi)
Nitrogen
Lo Hi
Nitrogen
Lo Hi
Wood Insulation
Flushing the Refrigerant Piping Procedure
1. Attach a pressure regulator on a nitrogen cylinder.
2. Connect the charge hose from the pressure regulator to the
outdoor unit liquid piping side service port before its connection
to the indoor or BD (Multi F MAX systems only) unit piping.
3. Open the main valve on the nitrogen cylinder and set the pres-
sure regulator to 0.5 MPa (72.5 psi).
4. Verify that the nitrogen is flowing through the piping correctly.
5. When flushing, block the open end of the piping with a wood
insulation block. When the pressure becomes too high, quickly
remove the block.
6. Repeat steps 4 and 5 until the piping is completely flushed and
clean.
7. Connect the charge hose from the pressure regulator to the out-
door unit gas piping side service port before its connection to the
indoor or BD (Multi F MAX systems only) unit piping.
8. Follow steps 3, 4, 5, and 6.
9. For systems with BD unit(s) (Multi F MAX only), each piping run
should be flushed individually before connecting the indoor units
(follow steps 3, 4, 5, and 6).
1LWURJHQÀXVKLQJLVVWURQJO\UHFRPPHQGHGDIWHUVROGHULQJ)RUHLJQPDWHULDOVLQWKHSLSLQJZLOOFDXVHV\VWHPPDOIXQFWLRQ
Figure 53: Flushing the Refrigerant Piping.
Flushing the Refrigerant Piping
REFRIGERANT PIPING PREPARATION

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LG Multi F MAX PMBD3640 and is the answer not in the manual?

LG Multi F MAX PMBD3640 Specifications

General IconGeneral
BrandLG
ModelMulti F MAX PMBD3640
CategoryAir Conditioner
LanguageEnglish

Related product manuals