Y-Branch accessory PMBL5620 is required when installing two branch distribution units in parallel on one Multi F MAX system.
MULTI F MAX BD UNIT
Multi F MAX Y-Branch Accessory
Table 317: Multi F MAX Y-Branch Specications.
Model Y-Branch Type
Port Identier (inch)
1 2 3
PMBL5620
Liquid Ø3/8 Ø3/8 Ø3/8
Vapor Ø3/4 Ø3/4 Ø3/4
Y-Branch Type
Dimensions (inch)
X Y
Liquid 13.80 3.24
Vapor 12.48 3.02
A
B
X
Y
1
2
3
A = To Outdoor Unit
B = To Branch Distribution Unit
1
2
3
Figure 33:Y-Branch Port Identier Diagram. Figure 34:Y-Branch Dimensions Diagram.
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.