Part Number 000015432 4/18 17
Electrical Service
General
n
Warning
All wiring must conform to local, state and national
codes.
Voltage
The maximum allowable voltage variation is ± 10% of the
rated voltage on the ice machine model/serial number
plate at start-up (when the electrical load is highest).
Fuse/Circuit Breaker
A separate fuse/circuit breaker must be provided for each
ice machine. Circuit breakers must be H.A.C.R. rated (does
not apply in Canada).
n
Warning
The ice machine must be grounded in accordance with
national and local electrical codes.
CIRCUIT AMPACITY
The minimum circuit ampacity is used to help select
the wire size of the electrical supply. (Minimum circuit
ampacity is not the ice machine’s running amp load.)
The wire size (or gauge) is also dependent upon location,
materials used, length of run, etc., so it must be
determined by a qualified electrician.
Self Contained Air-Cooled
Ice Machine
Voltage Phase
Cycle
Max. Fuse/
Circuit Breaker
Total Amps
CNF201
CNF202
115/1/60 15* 10.3*
230/1/50 15* 5.4*
*Indicates preliminary data - Model/Serial plate information
overrides the data in this chart.