EasyManuals Logo
Home>Manitowoc>Ice Maker>CVD0675

Manitowoc CVD0675 User Manual

Manitowoc CVD0675
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #172 background imageLoading...
Page #172 background image
–170–
Water Regulating Valve
Function
The water regulating valve maintains the freeze cycle
discharge pressure. The valve setting for the
CVD1476 condensing unit is 240 psig.
Check Procedure
1. Determine if the head pressure is high or low (refer
to “Operational Pressure Chart”.
2. Verify the condenser water meets specifications.
3. Adjust valve to increase or decrease discharge
pressure (if discharge pressure remains high refer
to “Headmaster Control Valve Diagnostics” before
replacing valve).
4. Determine the temperature of the liquid line
entering the receiver by feeling it. This line is
normally warm; “body temperature.”
5. Using the information gathered, refer to the list for
diagnosis.
Problem (Freeze Cycle)
Valve not maintaining discharge pressure.
Valve incorrectly set, dirty or defective. Adjust valve
to 240 psig, clean or replace valve.
Discharge pressure extremely high; Liquid line
entering receiver feels hot.
Water regulating valve incorrectly set or not
opening. Verify Head Pressure Control Valve
operation before changing water regulating valve.
Discharge pressure low, Liquid line entering
receiver feels warm to hot.
Ice machine low on charge. Refer to “Refrigerant
Charge Verification.”

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Manitowoc CVD0675 and is the answer not in the manual?

Manitowoc CVD0675 Specifications

General IconGeneral
BrandManitowoc
ModelCVD0675
CategoryIce Maker
LanguageEnglish

Related product manuals