Part Number STH038 5/12 151
HIGH PRESSURE CUTOUT (HPCO) CONTROL
FUNCTION
Stops the ice machine if subjected to excessive high-
side pressure. The HPCO control is normally closed,
and opens on a rise in discharge pressure.
SPECIFICATIONS.
SYMPTOM
Opening the HPCO will cause the control board to
initiate a 60 minute delay. The display counts down
from 60 minutes to 0 minutes, at which point the ice
machine attempts a restart. If the HPCO is closed the
ice machine will continue to run. If the HPCO remains
open after the 60 minute delay or reopens when the
compressor starts, the ice machine will start another
60 minute delay period. The ice machine will lockout
after 10 failed attempts.
1. Machine is off and the display indicates
“Delay XX min, HPCO Active”
2. Machine is running and the display indicates
“HPC Fault” and an alert triangle
Specifications
Cut-Out Cut-In
2413 kPa ±24.13 bar ±.69
350 psig ±10
Automatic Reset
Must be below 1723 kPa 17.23 bar (250 psig) to reset.