266 Part Number 80-1505-3 6/11
SY2074C/CVD2075 SERIES REMOTE AIR COOLED
NOTE: These characteristics may vary depending on
operating conditions.
CYCLE TIMES
24-HOUR ICE PRODUCTION
OPERATING PRESSURES
Freeze Time + Harvest Time = Cycle Time
Air Temp.
Entering
Condenser
°F/°C
Freeze Time
Harvest
Time
Water Temperature °F/°C
50/10 70/21 90/32
-20 to 70/
-29 to 21
8.8-9.6 9.7-10.6 10.8-11.8
.75-2.5
90/32 9.7-10.7 10.0-10.9 11.7-12.8
100/38 10.3-11.3 11.2-12.2 12.2-13.3
110/43 10.9-11.9 11.8-12.9 12.8-14.0
1
Times in minutes.
Air Temp.
Entering
Condenser
°F/°C
Water Temperature °F/°C
50/10 70/21 90/32
-20 to 70/
-29 to 21
2170 1995 1810
90/32 1985 1945 1690
100/38 1890 1760 1625
110/43 1800 1680 1560
1
Based on average ice weight of one Harvest cycle 15.5-16.75 lb.
(7.75-8.38 lb. per evaporator).
Air Temp.
Entering
Condenser
°F/°C
Freeze Cycle Harvest Cycle
Discharge
Pressure
psig
Suction
Pressure
psig
Discharge
Pressure
psig
Suction
Pressure
psig
-20 to 70/
-29 to 21
205-245 30-16 130-175 45-60
80/27 230-250 30-18 185-200 50-65
90/32 230-275 35-18 185-200 50-65
100/38 240-290 35-19 190-210 50-70
110/43 310-380 38-20 200-240 60-80
120/49 320-390 40-22 225-240 70-80
During low ambient conditions, it is normal for the head pressure
control valve to hunt (fluctuate up and down) on CVD condensing
units. Hunting varies by model and ambient temperature, but
generally settles out within the first 6 minutes of the freeze cycle