12 AGR 070A through 100A IOMM AGR-1
Evaporator Water Flow/Pressure Drop
Evaporator flow rate must fall between the minimum and maximum values shown in the evaporator
pressure drop table on page 12. Varying chilled water flow through the evaporator while the
compressor(s) are operating is not recommended.
Figure 8, Pressure Drop Curve
070
075 - 085
090 - 100
NOMINAL MAXIMUM MINIMUM
PD Flow PD Flow PD Flow
Unit
Size
(ft) of Water (gpm) (lps) (ft) of Water (gpm) (lps) (ft) of Water (gpm) (lps)
070AS 11.2 162 10.22 28.1 270 17.03 4.8 101 6.39
075AS 8.9 172 10.85 22.5 287 18.09 3.8 108 6.78
080AS 10.3 187 11.80 25.9 312 19.66 4.4 117 7.37
085AS 11.8 202 12.74 29.7 337 21.24 5.0 126 7.97
090AS 10.5 208 13.12 26.3 347 21.87 4.5 130 8.20
095AS 12.0 224 14.13 30.0 373 23.55 5.2 140 8.83
100AS 13.4 238 15.02 33.6 397 25.02 5.7 149 9.38
Minimum and maximum flows are established to ensure the Delta-T for each unit size falls within the 6 - 16°F range for proper
unit control. Contact factory for unit operation outside of minimum and maximum flows shown.