Page 30 of 32 OM 750
Table 25. UVC Configuration Parameters
Configuration Parameter Name Abr. Notes Default
LUI Menu
Item
Occupied Cooling Setpoint OCS 73
O
F (23
O
C)
Standby Cooling Setpoint SCS 77
O
F (25
O
C)
Unoccupied Cooling Setpoint UCS 82
O
F (28
O
C)
Occupied Heating Setpoint OHS 70
O
F (21
O
C)
Standby Heating Setpoint SHS 66
O
F (19
O
C)
Unoccupied Heating Setpoint UHS 61
O
F (16
O
C)
Local Bypass Time Tenant override 100 min
Space CO
2
Setpoint
CO2S 1200 PPM
Space Humidity Setpoint RHS
used with both active (reheat) and passive dehumidification
60% RH
sequences
Emergency Heat Enable
0 = disable, 1 = enable (uses auxiliary heat where primary heat is
1
not applicable)
Emergency Heat Setpoint EHS 54
O
F (12
O
C)
Emergency Heat Shutdown Configuration
0 = no emergency heat during shutdown, 1 = emergency heat
0
available during shutdown
Wall Sensor Type
0 = +/- 3°F, 1 = 55°F to 85°F0
Slave Type Configuration
0 = independent slave, 1 = dependent slave 0
OAD Min Position High-Speed Setpoint OADH
(this variable will be factory set to 5% open when the unit is ordered
20% open
with optional CO
2
DCV)
OAD Min Position Med-Speed Setpoint OADM
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
30% open
OAD Min Position Low-Speed Setpoint OADL
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
35% open
Exhaust Interlock OAD Min Position Setpoint EOAD
OA damper minimum position when the exhaust interlock input is
100% open
energized
Energize Exhaust Fan OAD Setpoint OADE defines position above which exhaust fan output will be energized 10% open
OAD Max Position Setpoint OAMX 100% open
OAD Lockout Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the
0
unit is ordered as a recirc unit with no OAD)
OA temperature below which the OA damper will remain closed
OAD Lockout Setpoint OALS (this variable will be factory set to 99
O
C when the unit is ordered 36
O
F (2
O
C)
as a recirc unit with no OAD)
Economizer Enable 0 = disable, 1 = enable 1
Economizer OA Temp Setpoint ETS 68
O
F (20
O
C)
Economizer IA/OA Temp Differential ETD 2
O
F (1
O
C)
Economizer OA Enthalpy Setpoint EES 25 btu/lb (58 kJ/kg)
Economizer IA/OA Enthalpy Differential EED 1.3 btu/lb (3 kJ/kg)
External BI-1 Configuration 0 = Unoccupied, 1 = Dewpoint/Humidity 0
External BI-3 Configuration 0 = Ventilation Lockout, 1 = Exhaust Interlock 0
Filter Alarm Enable 0 = disable, 1 = enable 0
Filter Change Hours Setpoint fan run hours between filter change alarms 700 hrs
Primary Cool Proportional Band 18
O
F (10
O
C)
Primary Cool Integral Time 180 sec
Secondary Cool Proportional Band 11
O
F (6
O
C)
UVC CONFIGURATION PARAMETERS
The UVC has been provided with a number of configuration variables
as listed in the following table. These configuration variables are stored
in UVC non-volatile memory.
For a description of supported network variables for each protocol refer
to Protocol Data Packet bulletin, see Table 4.
Continued on next page.
The software ServiceTools can be used to adjust parameters not
adjustable through the LUI.
NOTICE

Table of Contents

Other manuals for McQuay MicroTech II

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay MicroTech II and is the answer not in the manual?

McQuay MicroTech II Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech II
CategoryController
LanguageEnglish

Related product manuals