Page 30 of 32 OM 750
Table 25. UVC Configuration Parameters
Configuration Parameter Name Abr. Notes Default
LUI Menu
Item 햲
Occupied Cooling Setpoint OCS 73
O
F (23
O
C)
Standby Cooling Setpoint SCS 77
O
F (25
O
C)
Unoccupied Cooling Setpoint UCS 82
O
F (28
O
C)
Occupied Heating Setpoint OHS 70
O
F (21
O
C)
Standby Heating Setpoint SHS 66
O
F (19
O
C)
Unoccupied Heating Setpoint UHS 61
O
F (16
O
C)
Local Bypass Time Tenant override 100 min
Space CO
2
Setpoint
햳
CO2S 1200 PPM
Space Humidity Setpoint햳 RHS
used with both active (reheat) and passive dehumidification
60% RH
sequences
Emergency Heat Enable
0 = disable, 1 = enable (uses auxiliary heat where primary heat is
1
not applicable)
Emergency Heat Setpoint EHS 54
O
F (12
O
C)
Emergency Heat Shutdown Configuration
0 = no emergency heat during shutdown, 1 = emergency heat
0
available during shutdown
Wall Sensor Type
햳
0 = +/- 3°F, 1 = 55°F to 85°F0
Slave Type Configuration
햳
0 = independent slave, 1 = dependent slave 0
OAD Min Position High-Speed Setpoint OADH
(this variable will be factory set to 5% open when the unit is ordered
20% open
with optional CO
2
DCV)
OAD Min Position Med-Speed Setpoint OADM
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
30% open
OAD Min Position Low-Speed Setpoint OADL
(this variable is ignored when the unit is ordered with optional CO
2
DCV)
35% open
Exhaust Interlock OAD Min Position Setpoint EOAD
OA damper minimum position when the exhaust interlock input is
100% open
energized
Energize Exhaust Fan OAD Setpoint OADE defines position above which exhaust fan output will be energized 10% open
OAD Max Position Setpoint OAMX 100% open
OAD Lockout Enable
0 = disable, 1 = enable (this variable will be factory set to 1 when the
0
unit is ordered as a recirc unit with no OAD)
OA temperature below which the OA damper will remain closed
OAD Lockout Setpoint OALS (this variable will be factory set to –99
O
C when the unit is ordered 36
O
F (2
O
C)
as a recirc unit with no OAD)
Economizer Enable 0 = disable, 1 = enable 1
Economizer OA Temp Setpoint ETS 68
O
F (20
O
C)
Economizer IA/OA Temp Differential ETD 2
O
F (1
O
C)
Economizer OA Enthalpy Setpoint EES 25 btu/lb (58 kJ/kg)
Economizer IA/OA Enthalpy Differential EED 1.3 btu/lb (3 kJ/kg)
External BI-1 Configuration 0 = Unoccupied, 1 = Dewpoint/Humidity 0
External BI-3 Configuration 0 = Ventilation Lockout, 1 = Exhaust Interlock 0
Filter Alarm Enable 0 = disable, 1 = enable 0
Filter Change Hours Setpoint fan run hours between filter change alarms 700 hrs
Primary Cool Proportional Band 18
O
F (10
O
C)
Primary Cool Integral Time 180 sec
Secondary Cool Proportional Band 11
O
F (6
O
C)
UVC CONFIGURATION PARAMETERS
The UVC has been provided with a number of configuration variables
as listed in the following table. These configuration variables are stored
in UVC non-volatile memory.
For a description of supported network variables for each protocol refer
to Protocol Data Packet bulletin, see Table 4.
Continued on next page.
The software ServiceTools™ can be used to adjust parameters not
adjustable through the LUI.
NOTICE