Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
79
12.3 Typical malfunction solutions
1) High pressure and discharged temperature protection
High pressure and
discharged protection.
High pressure protection.
Blower stops rotating or rotates in
reversed direction in cooling mode,
water pump is not open or the flow.
Pressure controller is broken
or the joint is loose.
Fin heat exchanger in cooling mode is too
dirty or aged, or too heavy encrustation in
shell-tube for heating.
EXV, capillary and filter are
dirty, blocking.
Discharge temperature
protection.
See the analysis of
discharge temp. protection
malfunction.
Inspect fan motor and
capacitor (1phase) or
start up the water pump.
Replace press controller,
fixed joint.
Replace EXV, capillary
and filter.
There is air and filled refrigerant
too much in system.(Generally
occur after maintenance.)
Empty, vacuuming and
append refrigerant if
necessary.
Check if it happened
frequently, if yes, please
replace PCB.
Inform the customer
service center.