MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
84
9) Water flow detection malfunction
Water flow detection malfunction
Water pump didn’t open or error.
Didn’t open the valve in system.
The water flow detection switch
error.
Inform the customer service
center.
The water flow switch installed out
of criterion, result in mistaking
work.
Selected the capacity of water
pump is less (flow & head).
Designed the water pipe inner
dimension is too less.
Open the pump or change;
inspect the power supply or
control circuit of pump.
Replace the water flow
switch, inspect the
connecting wire.
Adjust the installation
position.
Remove superfluous valve
or forced it is always on.
The filter or water pipe is dirty, the
shell-tube heat exchanger scaled.
Clean filter, water pipe,
shell-tube heat exchanger.
Installed the 2-way valve quantity
is more than 50% of indoor unit
quantity.