Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
89
25/35/65/80/130kW module
A
B
D
C
Input of airflow
Input of airflow
unit
E
InputofairflowInputofairflow
unit
The recommend space parameter
● Space requirements for parallel installation of multiple scroll units
To avoid back flow of the air in the condenser and operational faults of the unit, the parallel installation of
multiple scroll units can follow the direction A and D as shown in the figure above, the spaces between the
unit and the obstacle are given in the figure above, and the space between adjacent scroll units should not
be less than 300mm; the installation can also follow the direction B and C as shown in the figure above, the
spaces between the unit and the obstacle are given in the figure above, and the space between adjacent
scroll units should not be less than 600mm; the installation can also follow the direction combination of A
and D, and B and C, the spaces between the unit and the obstacle are given in the figure above, the space
between adjacent scroll units in the direction A and D should not be less than 300mm, and the space
between adjacent scroll units in the direction B and C should not be less than 600mm.
If the spaces mentioned above cannot be met, the air passing from the unit to the coils may be restricted, or
back flow of air discharge may occur, and the performance of the unit may be affected, or the unit may fail to
operate.
Max unit combined
quantity
13.1.3 Installation foundation
The unit should be located on the horizontal foundation, the ground floor or the roof which can bear