6.1.55 J55 - Speed control mode setting error
Spot check interface
query
Error code is not
displayed
The faulty IDU stops. Other IDUs of the same system: operate normally.
ODU of the same system: operate normally.
The IDU is non constant air flow control, but its main control program sets the fan speed according
to the constant air flow control mode.
The IDU model is set incorrectly.
The IDU main control board is damaged.
J55
Is the fault cleared?
Replace the main control
board of the IDU
Fault cleared
Yes
No
Use the dedicated tooling (1)
to set the model code for the
main control board of IDU,
and power on the unit again
Note 1: For specialized tooling and instructions, please contact your local dealer or technical
support personnel.