V8 VRF Indoor Units
39
Troubleshooting Guide
Table 5.1: Error code(continues)
Error
code
Content
Error
code
Content
E32
The wireless temperature sensor short-circuits or cuts
off
U11
Unit model code not set
E33
The external room temperature sensor short-circuits
or cuts off
U12
Horsepower code not set
E61
Tcp (pre-cooled fresh air temperature sensor)
short-circuits or cuts off
U14
Horsepower code setting error
E62
Tph (pre-heated fresh air temperature sensor)
short-circuits or cuts off
U15
AHU Kit fan control input signal DIP setting error
E81
TA (outlet air temperature sensor) short-circuits or
cuts off
U38
Address code not detected
EA1
Outlet air humidity sensor fault
J01
Motor failed more than once
EA2
Return air humidity sensor fault
J1E
IPM (fan module) overcurrent protection
EA3
Upper wet bulb sensor fault
J11
Instantaneous overcurrent protection for phase current
EA4
Lower wet bulb sensor fault
J3E
Low bus voltage fault
EC1
R32 refrigerant leakage sensor fault
J31
High bus voltage fault
F01
T2A (heat exchanger inlet temperature sensor)
short-circuits or cuts off
J43
Phase current sample bias error
F11
T2 (heat exchanger middle temperature sensor)
short-circuits or cuts off
J45
Motor and IDU are unmatched
F12
T2 (heat exchanger middle temperature sensor)
overtemperature protection
J47
IPM and IDU are unmatched
F21
T2B (heat exchanger outlet temperature sensor)
short-circuits or cuts off
J5E
Motor startup failure
P71
Main control board EEPROM fault
J52
Motor blocking protection
P72
IDU display control board EEPROM fault
J55
Speed control mode setting error
U01
Locked (electronic lock)
J6E
Phase lack protection of motor
5.2 Operating Status Codes
Table 5.2:Operating Status Codes
Code
Content
Code
Content
d0
Oil return or preheating operation
d61
Remote shutdown
dC
Self-cleaning
d71
IDU backup operation
dd
Mode conflict (V8 communication protocol adopted)
d72
ODU backup operation
dF
Defrosting
OTA
Main control program upgrading
d51
Static pressure detection
d61
Remote shutdown