Midea
V8
Series VRF Indoor Units
6.1.42 U11 - Unit model code not set
Panel, display box, and wired controller
1) The faulty IDU stops running.
2) Other IDUs of the same system:
If the address for the faulty IDU has been set, other IDUs will operate normally.
Otherwise, other IDUs will encounter the following situations: The fan continues running, the EXV is
closed, and ODU error code "A51" is displayed (V6 platform IDU displays the code "Ed").
ODU of the same system:
If the address for the faulty IDU has been set, the ODU will operate normally.
Otherwise, the ODU will display the error code "C26" (number of IDUs reduced) (V6 platform ODU
displays the code "H7")
When detecting that the unit model code for IDU main control board is not set
The unit model code has not been set after replacing the IDU main control board.
The new IDU main control board is damaged.
U11
Is the fault cleared?
Replace the main control
board of the IDU
Fault cleared
Yes
No
Use the dedicated tooling
(1) to set the model code
for the main control
board of IDU, and power
on the unit again
Note 1: For specialized tooling and instructions, please contact your local dealer or technical support
personnel.